A Model of Output Power Control Method for Fault Ride-Through in a Single-Phase NPC Inverter-Based Power Conditioning System with IPOS DAB Converter and Battery
Grid-tied inverters must satisfy fault ride-through (FRT) requirements to ensure grid stability during voltage disturbances. However, most existing FRT-related studies have focused on reactive current injection or voltage support functions, with few addressing how the active power reference should be dynamically controlled during voltage dips. In addition, few systems enable bidirectional power transfer or provide comprehensive verification under deep voltage dips. To address this issue, this paper proposes an output power control method for FRT in a single-phase neutral-point-clamped (NPC) inverter-based PCS consisting of an input-parallel output-series (IPOS) dual-active-bridge (DAB) converter and a battery. The proposed PCS dynamically reduces the output power reference according to the retained voltage while maintaining the inverter current within the rated limit, thereby ensuring stable operation. Computer simulations were conducted using Altair PSIM to verify the effectiveness of the proposed method. The results confirmed that the PCS satisfied the FRT requirements for all post-fault voltage levels. The injected current returned to its pre-fault value within 20 ms and 90 ms for 20% and 0% voltage dips, respectively, complying with the required recovery times. The proposed control method enhances grid resilience and maintains power quality in single-phase low-voltage distribution systems.
Authors
- Tomokazu Mishima (ORCID: https://orcid.org/0000-0002-5170-277X)
- Reo Emoto
- Hiroaki Yamada (ORCID: https://orcid.org/0000-0001-5803-8632)
Institutions
- Yamaguchi University (JP)
Publication Details
- Journal
- Electronics
- Published
- 2025-10-31
- DOI
- https://doi.org/10.3390/electronics14214291
- Primary Topic
- Microgrid Control and Optimization
- Type
- article
- Field-Weighted Citation Impact
- 0.00