Data halls within data centers are high-risk and high-value facilities. However, ensuring fire safety has proven challenging owing to the performance limitations of gas-suppression systems. In this study, the fire-suppression performance and design validity of a single-interlock pre-action sprinkler system were quantitatively assessed via a fire dynamics simulator (FDS) and SprinkCALC simulations. The FDS analysis revealed that, whereas the gas-suppression system showed limited effectiveness in controlling the HRR and reducing temperature owing to its one-time discharge, the sprinkler system demonstrated a meaningful effect on temperature reduction through its continuous cooling action. However, the control effect on the HRR was minimal, thus indicating that the sprinkler system is limited in verifying its effectiveness for overall fire control. Furthermore, the SprinkCALC analysis confirmed that the pre-action sprinkler system satisfied both the NFPA-required discharge time of within 50 s and the design density criteria. The results of this study suggest the potential applicability of sprinkler systems as a future fire-protection strategy for data centers.

Authors

Publication Details

Journal
Fire Science and Engineering
Published
2025-10-31
DOI
https://doi.org/10.7731/kifse.38d2f344
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Preliminary Study on Applicability of Pre-Action Sprinkler Systems in Data Halls of Data Centers

Min Hyuk Choi, Jin-seock Seo, Sunnie Haam
Fire Science and Engineering
Fire dynamics and safety research
article

Preliminary Study on Applicability of Pre-Action Sprinkler Systems in Data Halls of Data Centers

Min Hyuk Choi, Jin-seock Seo, Sunnie Haam
article en

Abstract

Data halls within data centers are high-risk and high-value facilities. However, ensuring fire safety has proven challenging owing to the performance limitations of gas-suppression systems. In this study, the fire-suppression performance and design validity of a single-interlock pre-action sprinkler system were quantitatively assessed via a fire dynamics simulator (FDS) and SprinkCALC simulations. The FDS analysis revealed that, whereas the gas-suppression system showed limited effectiveness in controlling the HRR and reducing temperature owing to its one-time discharge, the sprinkler system demonstrated a meaningful effect on temperature reduction through its continuous cooling action. However, the control effect on the HRR was minimal, thus indicating that the sprinkler system is limited in verifying its effectiveness for overall fire control. Furthermore, the SprinkCALC analysis confirmed that the pre-action sprinkler system satisfied both the NFPA-required discharge time of within 50 s and the design density criteria. The results of this study suggest the potential applicability of sprinkler systems as a future fire-protection strategy for data centers.

Fire Science and EngineeringVol. 39(5)
Openalex Percentile: Top 61%
Fire dynamics and safety research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.