Research on the characteristics of multi-infeed DC system with hybrid commutation converter suppressing successive commutation failure

• This paper addresses the problem of successive commutation failure in multi-infeed DC system. • Studies have shown that hybrid commutated converter is effective greatly for successive commutation failure. • The risk of successive commutation failure is analysed and the mechanism of HCC to suppress the risk is analysed . • Because of active turn-off, less reactive power, faster recovery, successive commutation failure can be supressed by HCC. • Solving successive commutation failure can suppress the power transmission blocking and improve security & stability. In view of the problem of successive commutation failure in multi-infeed direct current systems, this paper investigates the commutation characteristics of hybrid commutation convert technology and its application in mitigating successive commutation failure, with a case study based on the Lingbao Converter Station modification project in the Henan grid. First, the operational mode of hybrid commutated converter is proposed, and its low reactive power consumption reduced by 20% is calculated and compared with that of a line commutated converter. Then, the mechanism of successive commutation failure in Henan grid is analyzed using an equivalent grid model. The hybrid commutation convert technique is introduced as a solution to successive commutation failure due to its advantages, including complete commutation failure mitigation, fast post-fault recovery, and reduced reactive power consumption. Finally, the effectiveness of the proposed operational mode is verified through Real-Time Digital Simulator simulation tests. A simulation model of both hybrid commutation converter and line commutation converter-based high voltage direct current system is developed, and the commutation characteristics during fault and recovery are analysed. Additionally, the efficacy of hybrid commutation converter in suppressing successive commutation failure in the multi-infeed direct current system is evaluated through CloudPSS-based grid simulations.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-10-31
DOI
https://doi.org/10.1016/j.ijepes.2025.111307
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on the characteristics of multi-infeed DC system with hybrid commutation converter suppressing successive commutation failure

Xiaoguang Wei, Xuejiao Han, Kangsheng Cui, Jian Zhong Cui et al.
International Journal of Electrical Power & Energy Systems
HVDC Systems and Fault Protection
article

Research on the characteristics of multi-infeed DC system with hybrid commutation converter suppressing successive commutation failure

Xiaoguang Wei, Xuejiao Han, Kangsheng Cui, Jian Zhong Cui, P. D. Zhao, Zhanqing Yu, Long Zhang, Zhichang Yuan
article en

Abstract

• This paper addresses the problem of successive commutation failure in multi-infeed DC system. • Studies have shown that hybrid commutated converter is effective greatly for successive commutation failure. • The risk of successive commutation failure is analysed and the mechanism of HCC to suppress the risk is analysed . • Because of active turn-off, less reactive power, faster recovery, successive commutation failure can be supressed by HCC. • Solving successive commutation failure can suppress the power transmission blocking and improve security & stability. In view of the problem of successive commutation failure in multi-infeed direct current systems, this paper investigates the commutation characteristics of hybrid commutation convert technology and its application in mitigating successive commutation failure, with a case study based on the Lingbao Converter Station modification project in the Henan grid. First, the operational mode of hybrid commutated converter is proposed, and its low reactive power consumption reduced by 20% is calculated and compared with that of a line commutated converter. Then, the mechanism of successive commutation failure in Henan grid is analyzed using an equivalent grid model. The hybrid commutation convert technique is introduced as a solution to successive commutation failure due to its advantages, including complete commutation failure mitigation, fast post-fault recovery, and reduced reactive power consumption. Finally, the effectiveness of the proposed operational mode is verified through Real-Time Digital Simulator simulation tests. A simulation model of both hybrid commutation converter and line commutation converter-based high voltage direct current system is developed, and the commutation characteristics during fault and recovery are analysed. Additionally, the efficacy of hybrid commutation converter in suppressing successive commutation failure in the multi-infeed direct current system is evaluated through CloudPSS-based grid simulations.

International Journal of Electrical Power & Energy SystemsVol. 172
Tsinghua Sichuan Energy Internet Research Institute (CN), Xi'an Jiaotong University (CN), Tsinghua University (CN)
Openalex Percentile: Top 68%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.