Influence of Control Strategies on the Output Impedance of Grid-Connected LCL Inverters in the <i>dq</i> -Domain

This paper presents an analytical method for deriving the <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">dq</i>-domain output impedance matrix (dqOIM) of a grid-connected LCL inverter operating in grid-following mode. Combined with the grid impedance matrix (GIM), the dqOIM—dependent on the current control system and the phase-locked loop (PLL)—enables small-signal stability assessment of the inverter–grid interface using the generalized Nyquist criterion. The paper also examines the influence of three previously proposed control strategies on the dqOIM and overall system stability. These strategies differ in how they address <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">dq</i>-axis coupling in current control and damping of the LCL filter resonance. Their tuning methods typically focus on the internal current-loop stability, neglecting PLL effects and grid impedance variations, and consequently overlooking external stability of the inverter–grid connection. Results show that the dqOIM q-q element exhibits negative resistance behavior within the PLL bandwidth across all evaluated controllers, consistent with observations for L-type inverters. The q-d element displays a similar trend, further challenging external stability. Such destabilizing effects, however, can be alleviated through established measures, including virtual impedance insertion, PLL bandwidth reduction, or auxiliary active-damping loops. These findings suggest that advanced decoupling and damping techniques may increase susceptibility to external instability. Overall, the study underscores the role of dqOIM as a valuable tool for control design and stability assessment of grid-connected inverters. Theoretical results are validated through hardware-in-the-loop simulations and experimental tests.

Authors

Institutions

Publication Details

Journal
IEEE Access
Published
2025-01-01
DOI
https://doi.org/10.1109/access.2025.3627125
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Influence of Control Strategies on the Output Impedance of Grid-Connected LCL Inverters in the dq -Domain

Luan A. C. Mendonça, António J. Marques Cardoso, Filipe A. da C. Bahia, André P. N. Tahim et al.
IEEE Access
Microgrid Control and Optimization
article

Influence of Control Strategies on the Output Impedance of Grid-Connected LCL Inverters in the dq -Domain

Luan A. C. Mendonça, António J. Marques Cardoso, Filipe A. da C. Bahia, André P. N. Tahim, Fabiano F. Costa, Diego O. Cardoso
article en

Abstract

This paper presents an analytical method for deriving the <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">dq</i>-domain output impedance matrix (dqOIM) of a grid-connected LCL inverter operating in grid-following mode. Combined with the grid impedance matrix (GIM), the dqOIM—dependent on the current control system and the phase-locked loop (PLL)—enables small-signal stability assessment of the inverter–grid interface using the generalized Nyquist criterion. The paper also examines the influence of three previously proposed control strategies on the dqOIM and overall system stability. These strategies differ in how they address <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">dq</i>-axis coupling in current control and damping of the LCL filter resonance. Their tuning methods typically focus on the internal current-loop stability, neglecting PLL effects and grid impedance variations, and consequently overlooking external stability of the inverter–grid connection. Results show that the dqOIM q-q element exhibits negative resistance behavior within the PLL bandwidth across all evaluated controllers, consistent with observations for L-type inverters. The q-d element displays a similar trend, further challenging external stability. Such destabilizing effects, however, can be alleviated through established measures, including virtual impedance insertion, PLL bandwidth reduction, or auxiliary active-damping loops. These findings suggest that advanced decoupling and damping techniques may increase susceptibility to external instability. Overall, the study underscores the role of dqOIM as a valuable tool for control design and stability assessment of grid-connected inverters. Theoretical results are validated through hardware-in-the-loop simulations and experimental tests.

IEEE AccessVol. 13
Universidade Federal da Bahia (BR), University of Beira Interior (PT)
Openalex Percentile: Top 60%
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.