• Optimal condition for supine rest is 29 °C with 0.4 m/s airflow in this study. • Fan cooling saves 25.3 % energy and outperforms HVAC in comfort. • Air temperature and air speed significantly affect distal skin temperature. • Fan cooling is more effective at lower ambient temperatures. Short-term supine rest commonly occurs in settings such as airport rest pods, midday breaks, and hospital wards, where conventional air-conditioning often struggles to provide efficient comfort. Fan-based personal comfort systems offer a practical solution, but findings from seated postures cannot be directly generalized to supine rest due to differences in thermoregulation and heat transfer. This study aimed to determine optimal fan conditions and clarify the physiological basis of comfort during short-term supine rest. A two-factorial experiment with 14 healthy adults tested nine combinations of air temperature (26, 29, 31 °C) and air speed (0, 0.4, 0.8 m/s). Local skin temperatures and subjective thermal perception votes were collected over 40 min. The results showed that 29 °C with 0.4 m/s airflow was the optimal condition, yielding the highest comfort and reducing HVAC energy use by 25.3 % compared with 26 °C without airflow. Both air temperature and airflow significantly influenced thermal perception and local skin temperatures, with distal body sites showing greater sensitivity to the thermal environment. Interaction effects indicated that airflow alleviated heat discomfort, but its cooling benefit diminished as air temperature increased. Overall, this study provides empirical evidence that fan cooling can enhance thermal comfort and energy efficiency in short-term supine rest, offering valuable guidance for future design standards.

Authors

Institutions

Publication Details

Journal
Building and Environment
Published
2025-10-29
DOI
https://doi.org/10.1016/j.buildenv.2025.113916
Primary Topic
Pressure Ulcer Prevention and Management
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Fan cooling as an effective strategy to enhance thermal comfort and energy efficiency for short-term supine rest

Xudong Zhang, Guoquan Lv, Charlie Huizenga, Xinbo Xu et al.
Building and Environment
Pressure Ulcer Prevention and Management
article

Fan cooling as an effective strategy to enhance thermal comfort and energy efficiency for short-term supine rest

Xudong Zhang, Guoquan Lv, Charlie Huizenga, Xinbo Xu, Hui Zhang, Xue Zhai
article en

Abstract

• Optimal condition for supine rest is 29 °C with 0.4 m/s airflow in this study. • Fan cooling saves 25.3 % energy and outperforms HVAC in comfort. • Air temperature and air speed significantly affect distal skin temperature. • Fan cooling is more effective at lower ambient temperatures. Short-term supine rest commonly occurs in settings such as airport rest pods, midday breaks, and hospital wards, where conventional air-conditioning often struggles to provide efficient comfort. Fan-based personal comfort systems offer a practical solution, but findings from seated postures cannot be directly generalized to supine rest due to differences in thermoregulation and heat transfer. This study aimed to determine optimal fan conditions and clarify the physiological basis of comfort during short-term supine rest. A two-factorial experiment with 14 healthy adults tested nine combinations of air temperature (26, 29, 31 °C) and air speed (0, 0.4, 0.8 m/s). Local skin temperatures and subjective thermal perception votes were collected over 40 min. The results showed that 29 °C with 0.4 m/s airflow was the optimal condition, yielding the highest comfort and reducing HVAC energy use by 25.3 % compared with 26 °C without airflow. Both air temperature and airflow significantly influenced thermal perception and local skin temperatures, with distal body sites showing greater sensitivity to the thermal environment. Interaction effects indicated that airflow alleviated heat discomfort, but its cooling benefit diminished as air temperature increased. Overall, this study provides empirical evidence that fan cooling can enhance thermal comfort and energy efficiency in short-term supine rest, offering valuable guidance for future design standards.

Building and EnvironmentVol. 287
Tianjin University (CN), National University of Singapore (SG), Shanghai Jiao Tong University (CN), Zhejiang Province Institute of Architectural Design and Research (CN), Zhejiang University (CN), University of California, Berkeley (US)
Openalex Percentile: Top 55%
Pressure Ulcer Prevention and Management
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.