Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers

The short-circuit withstanding capability of a transformer is a critical indicator for evaluating its operational reliability. This study investigates the influence of the low-voltage winding height, a key structural parameter, on the electromagnetic forces induced by short-circuit currents and the resultant short-circuit withstand capability. First, theoretical calculation formulas for the transformer leakage magnetic field and winding electromagnetic forces were derived, establishing a foundation for subsequent analysis. Subsequently, two 110 kV transformers, identical in all structural parameters except for their low-voltage winding heights, were selected as case studies. Three-dimensional finite element models were constructed to perform detailed simulations and a comparative analysis of the leakage magnetic field distribution and electromagnetic forces under short-circuit conditions. Finally, practical short-circuit tests were conducted on both transformers for experimental validation, monitoring and comparison of their short-circuit reactance variation curves. Furthermore, a CNN-LSTM model, utilizing the winding axial height of a 110 kV three-phase three-limb transformer as the characteristic parameter, is developed to detect short-circuit fault damage in such transformers with varying winding heights. Through a combined approach of theoretical analysis, simulation, and experimental verification, this study confirms that the low-voltage winding height was a crucial factor affecting the transformer's short-circuit withstand capability of the transformer. Studies have shown that with the increase in the height of low-voltage windings, the leakage magnetic flux of the low-voltage windings increases by 36%, the radial electromagnetic force increases by 37.5%, and the axial electromagnetic force increases by 8.5%. Excessively tall windings amplify radial electromagnetic forces, compromising mechanical stability and consequently increasing the risk of damage during short-circuit faults.

Authors

Institutions

Publication Details

Journal
Sensors
Published
2025-10-23
DOI
https://doi.org/10.3390/s25216528
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers

Ziyuan Xin, Sijun Wang, Chih-Che Tai, Tian Tian et al.
Sensors
Power Transformer Diagnostics and Insulation
article

Study on the Influence of Winding Height on the Short-Circuit Withstand Capability of 110 kV Transformers

Ziyuan Xin, Sijun Wang, Chih-Che Tai, Tian Tian, Xiaokang Wang, Yukun Ma, Dezhi Chen, Xiu Zhou
article en

Abstract

The short-circuit withstanding capability of a transformer is a critical indicator for evaluating its operational reliability. This study investigates the influence of the low-voltage winding height, a key structural parameter, on the electromagnetic forces induced by short-circuit currents and the resultant short-circuit withstand capability. First, theoretical calculation formulas for the transformer leakage magnetic field and winding electromagnetic forces were derived, establishing a foundation for subsequent analysis. Subsequently, two 110 kV transformers, identical in all structural parameters except for their low-voltage winding heights, were selected as case studies. Three-dimensional finite element models were constructed to perform detailed simulations and a comparative analysis of the leakage magnetic field distribution and electromagnetic forces under short-circuit conditions. Finally, practical short-circuit tests were conducted on both transformers for experimental validation, monitoring and comparison of their short-circuit reactance variation curves. Furthermore, a CNN-LSTM model, utilizing the winding axial height of a 110 kV three-phase three-limb transformer as the characteristic parameter, is developed to detect short-circuit fault damage in such transformers with varying winding heights. Through a combined approach of theoretical analysis, simulation, and experimental verification, this study confirms that the low-voltage winding height was a crucial factor affecting the transformer's short-circuit withstand capability of the transformer. Studies have shown that with the increase in the height of low-voltage windings, the leakage magnetic flux of the low-voltage windings increases by 36%, the radial electromagnetic force increases by 37.5%, and the axial electromagnetic force increases by 8.5%. Excessively tall windings amplify radial electromagnetic forces, compromising mechanical stability and consequently increasing the risk of damage during short-circuit faults.

SensorsVol. 25(21)
Shenyang University of Technology (CN), Shanghai Electric (China) (CN)
Openalex Percentile: Top 70%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.