Assessment of the performance of ultralow‐<scp>GWP</scp> refrigerants in a two‐stage heat pump system using simulation and <scp>MCMD</scp>

Abstract The Kigali Amendment's mandate to phase down high‐GWP refrigerants highlights the urgent need for sustainable alternatives in cold climate heat pumps, which are critical for delivering efficient heating in severely cold regions. This study evaluates ultralow‐GWP refrigerants—R‐290, R‐152a, R‐161, R‐1234yf, and R‐1234ze(E)—for application in a two‐stage vapor injection heat pump operating at outdoor temperatures as low as −20 °C and a condenser temperature of 52 °C. The methodology integrates modeling and simulation with thermodynamic and exergy analyses, total equivalent warming impact (TEWI) assessment, and a TOPSIS‐based multicriteria decision‐making (MCDM) approach. Results show that R‐152a achieves the highest COP (2.92) and the lowest TEWI (9078.78 kg CO 2 e), followed by R‐290 (COP = 2.81, TEWI = 9345.6 kg CO 2 e), while R‐161 shows the lowest COP (2.64). A trade‐off in volumetric heating capacity is observed: R‐152a delivers 3.2 MJ/m 3 versus 3.78 MJ/m 3 for R‐161. Exergy efficiency increases with ambient temperature; for example, R‐152a improves from 0.355 to 0.383 as temperature rises from −20 °C to 0 °C. The TOPSIS ranking confirms R‐152a as the top performer (score = 0.642), closely followed by R‐290 (0.637). All refrigerants evaluated show acceptable performance for cold‐climate use. Notably, R‐152a and R‐290 emerge as climate‐friendly, high‐performance candidates. Unlike prior studies that rely primarily on single‐criterion comparisons, this work introduces a novel integrated framework combining thermodynamic, exergy, environmental, and MCDM analyses to guide refrigerant selection for sustainable heating in cold climates.

Authors

Institutions

Publication Details

Journal
Environmental Progress & Sustainable Energy
Published
2025-10-21
DOI
https://doi.org/10.1002/ep.70132
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Assessment of the performance of ultralow‐GWP refrigerants in a two‐stage heat pump system using simulation and MCMD

Kuanrong Qiu, Martin Thomas
Environmental Progress & Sustainable Energy
Refrigeration and Air Conditioning Technologies
article

Assessment of the performance of ultralow‐GWP refrigerants in a two‐stage heat pump system using simulation and MCMD

Kuanrong Qiu, Martin Thomas
article en

Abstract

Abstract The Kigali Amendment's mandate to phase down high‐GWP refrigerants highlights the urgent need for sustainable alternatives in cold climate heat pumps, which are critical for delivering efficient heating in severely cold regions. This study evaluates ultralow‐GWP refrigerants—R‐290, R‐152a, R‐161, R‐1234yf, and R‐1234ze(E)—for application in a two‐stage vapor injection heat pump operating at outdoor temperatures as low as −20 °C and a condenser temperature of 52 °C. The methodology integrates modeling and simulation with thermodynamic and exergy analyses, total equivalent warming impact (TEWI) assessment, and a TOPSIS‐based multicriteria decision‐making (MCDM) approach. Results show that R‐152a achieves the highest COP (2.92) and the lowest TEWI (9078.78 kg CO 2 e), followed by R‐290 (COP = 2.81, TEWI = 9345.6 kg CO 2 e), while R‐161 shows the lowest COP (2.64). A trade‐off in volumetric heating capacity is observed: R‐152a delivers 3.2 MJ/m 3 versus 3.78 MJ/m 3 for R‐161. Exergy efficiency increases with ambient temperature; for example, R‐152a improves from 0.355 to 0.383 as temperature rises from −20 °C to 0 °C. The TOPSIS ranking confirms R‐152a as the top performer (score = 0.642), closely followed by R‐290 (0.637). All refrigerants evaluated show acceptable performance for cold‐climate use. Notably, R‐152a and R‐290 emerge as climate‐friendly, high‐performance candidates. Unlike prior studies that rely primarily on single‐criterion comparisons, this work introduces a novel integrated framework combining thermodynamic, exergy, environmental, and MCDM analyses to guide refrigerant selection for sustainable heating in cold climates.

Environmental Progress & Sustainable Energy
Natural Resources Canada (CA)
Openalex Percentile: Top 69%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.