Active arc suppression method for stator ground fault in multi-generator common-bus system on offshore oil platforms

• The proposed method injects dual-frequency compensation at generator terminal, enabling a single device to suppress ground faults for multiple generators. • A selective fault location criterion is proposed, which utilizes the variation of terminal zero-sequence current before and after arc suppression to identify the faulty generator. • Simulation and experiment results confirm the method's robustness against different fault conditions, demonstrating strong engineering applicability. Generators on offshore oil platforms are often subjected to vibrations caused by wave impacts, which lead to frequent stator ground faults and arc generation. The generator system typically adopts a multi-generator common-bus configuration. If the conventional active arc suppression method based on neutral-point voltage regulation is used, high equipment cost and maintenance complexity are introduced. An active arc suppression method based on terminal voltage regulation is proposed in this paper. The arc suppression device is installed at the terminal side bus. When the stator ground fault occurs in any generator, the fault point voltage is regulated to zero by controlling the terminal voltage of the generator. Reliable arc suppression can thus be achieved, while significantly reducing the total installed capacity and the number of configured devices required for arc suppression. A selective fault location criterion based on the phase of the variation of terminal zero-sequence current before and after arc suppression is also proposed. The faulty generator can be identified after arc suppression. The effectiveness of the proposed method is verified through simulation and experimental results.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2025-10-21
DOI
https://doi.org/10.1016/j.ijepes.2025.111256
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Active arc suppression method for stator ground fault in multi-generator common-bus system on offshore oil platforms

Jian Qiao, Chenxiao Tang, Xin Yin, Chunguang Ren et al.
International Journal of Electrical Power & Energy Systems
Power Systems Fault Detection
article

Active arc suppression method for stator ground fault in multi-generator common-bus system on offshore oil platforms

Jian Qiao, Chenxiao Tang, Xin Yin, Chunguang Ren, Yikai Wang, Xianggen Yin, Zengping Wang
article en

Abstract

• The proposed method injects dual-frequency compensation at generator terminal, enabling a single device to suppress ground faults for multiple generators. • A selective fault location criterion is proposed, which utilizes the variation of terminal zero-sequence current before and after arc suppression to identify the faulty generator. • Simulation and experiment results confirm the method's robustness against different fault conditions, demonstrating strong engineering applicability. Generators on offshore oil platforms are often subjected to vibrations caused by wave impacts, which lead to frequent stator ground faults and arc generation. The generator system typically adopts a multi-generator common-bus configuration. If the conventional active arc suppression method based on neutral-point voltage regulation is used, high equipment cost and maintenance complexity are introduced. An active arc suppression method based on terminal voltage regulation is proposed in this paper. The arc suppression device is installed at the terminal side bus. When the stator ground fault occurs in any generator, the fault point voltage is regulated to zero by controlling the terminal voltage of the generator. Reliable arc suppression can thus be achieved, while significantly reducing the total installed capacity and the number of configured devices required for arc suppression. A selective fault location criterion based on the phase of the variation of terminal zero-sequence current before and after arc suppression is also proposed. The faulty generator can be identified after arc suppression. The effectiveness of the proposed method is verified through simulation and experimental results.

International Journal of Electrical Power & Energy SystemsVol. 172
North China Electric Power University (CN), Wuhan University of Technology (CN), Huazhong University of Science and Technology (CN), Taiyuan University of Technology (CN)
Openalex Percentile: Top 62%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.