Experimental Methods and Equivalence Research on Inter-Turn Short Circuits in Power Transformers
Inter-turn short-circuit faults in power transformers generate enormous short-circuit currents within the affected turns, making full-scale experimental investigations impractical. To address this issue, this study proposes an experimental method utilizing a third external short-circuit winding to simulate inter-turn faults through structural improvements in winding configuration and conductor current-carrying capacity. A simulation calculation model for transformer inter-turn short circuits was first established to investigate the equivalence between the proposed equivalent fault model and actual fault conditions under varying short-circuit positions and proportions. Simulation results demonstrate that both models exhibit consistent primary/secondary winding currents, short-circuit turn currents, and spatial radial leakage magnetic field distributions post-fault, with average errors less than 5%. Subsequently, an experimental platform for inter-turn short-circuit fault simulation was constructed. Current and leakage magnetic field measurements under different fault positions and proportions were validated against simulation data, confirming the proposed method’s equivalence. This approach provides an effective pathway for investigating fault characteristics and monitoring methodologies of transformer inter-turn short circuits.
Authors
- Yuanming Shuai
- Zhengyang Zhang (ORCID: https://orcid.org/0000-0002-2295-0715)
- Lanjun Yang (ORCID: https://orcid.org/0000-0001-9347-2354)
- Dongyang Wu (ORCID: https://orcid.org/0000-0002-2570-6494)
- Chun Yang (ORCID: https://orcid.org/0009-0009-7741-9735)
Institutions
- Tebian Electric Apparatus (China) (CN)
- Tianjin Energy Investment Group (China) (CN)
- Xi'an Jiaotong University (CN)
Publication Details
- Journal
- Energies
- Published
- 2025-10-16
- DOI
- https://doi.org/10.3390/en18205453
- Primary Topic
- Power Transformer Diagnostics and Insulation
- Type
- article
- Field-Weighted Citation Impact
- 0.00