Dynamic simulation of a hydropower plant cluster with a pumped-storage unit: A case study in Greece

• A dynamic Modelica model for both conventional and pumped-storage HPPs is developed. • The model captures frequency response (±3.4 mHz frequency deviations), control actions, and operational constraints (voltage within ±0.06% of nominal). • Novel clustered operation of Greek HPPs (Ilarionas, Pournari, Thissavros) under real demand profiles. • The model supports analysis of HPPs, both long-term and short-term. • Droop control enables stable frequency regulation in multi-unit systems (20% load disturbance tested). Pumped-storage hydropower (PSH) offers significant advantages to modern power systems by providing large-scale, long-duration energy storage with high efficiency and long service life. This paper presents a dynamic simulation study of a Greek hydropower cluster comprising three plants, interconnected with the transmission grid and including both conventional and pumped-storage hydropower units. The model is implemented in Modelica, parameterised with plant-specific data, and driven by actual transmission-level profiles for grid representation. Two operation modes are analysed: (i) long-term scheduling with variable load profiles, and (ii) short-term response to a 20% step load disturbance. The long-term simulations reproduce actual system behaviour, with frequency deviations constrained within ±3.4 mHz and voltage fluctuations within ±0.06%. In the short-term case, coordinated hydropower operation improves frequency nadir by 0.38% (49.603 Hz compared to 49.415 Hz without hydropower), reduces the rate of change of frequency by 88%, and shortens recovery time by 40%. These results demonstrate the complementary roles of conventional and pumped-storage units in primary frequency control and underline the contribution of clustered hydropower to ancillary services and overall grid reliability.

Authors

Institutions

Publication Details

Journal
Energy Nexus
Published
2025-10-17
DOI
https://doi.org/10.1016/j.nexus.2025.100572
Primary Topic
Cavitation Phenomena in Pumps
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Dynamic simulation of a hydropower plant cluster with a pumped-storage unit: A case study in Greece

Renos Rotas, Petros Iliadis, Nikolaos Nikolopoulos, Panagiotis Grammelis et al.
Energy Nexus
Cavitation Phenomena in Pumps
article

Dynamic simulation of a hydropower plant cluster with a pumped-storage unit: A case study in Greece

Renos Rotas, Petros Iliadis, Nikolaos Nikolopoulos, Panagiotis Grammelis, Spyridoula Trakaki
article en

Abstract

• A dynamic Modelica model for both conventional and pumped-storage HPPs is developed. • The model captures frequency response (±3.4 mHz frequency deviations), control actions, and operational constraints (voltage within ±0.06% of nominal). • Novel clustered operation of Greek HPPs (Ilarionas, Pournari, Thissavros) under real demand profiles. • The model supports analysis of HPPs, both long-term and short-term. • Droop control enables stable frequency regulation in multi-unit systems (20% load disturbance tested). Pumped-storage hydropower (PSH) offers significant advantages to modern power systems by providing large-scale, long-duration energy storage with high efficiency and long service life. This paper presents a dynamic simulation study of a Greek hydropower cluster comprising three plants, interconnected with the transmission grid and including both conventional and pumped-storage hydropower units. The model is implemented in Modelica, parameterised with plant-specific data, and driven by actual transmission-level profiles for grid representation. Two operation modes are analysed: (i) long-term scheduling with variable load profiles, and (ii) short-term response to a 20% step load disturbance. The long-term simulations reproduce actual system behaviour, with frequency deviations constrained within ±3.4 mHz and voltage fluctuations within ±0.06%. In the short-term case, coordinated hydropower operation improves frequency nadir by 0.38% (49.603 Hz compared to 49.415 Hz without hydropower), reduces the rate of change of frequency by 88%, and shortens recovery time by 40%. These results demonstrate the complementary roles of conventional and pumped-storage units in primary frequency control and underline the contribution of clustered hydropower to ancillary services and overall grid reliability.

Energy NexusVol. 20
Democritus University of Thrace (GR), Aristotle University of Thessaloniki (GR), Centre for Research and Technology Hellas (GR)
Openalex Percentile: Top 66%
Cavitation Phenomena in Pumps
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.