Improved Variable-Quantity Distance Protection Method Based on Impedance Compensation Under Phase-to-phase Fault Conditions
In synchronous condenser-wind farm integrated transmission systems, the inherent asymmetry between positiveand negative-sequence impedances constitutes a critical limitation for the proper operation of sudden-impedance-based distance protection. To address this challenge, this paper proposes an enhanced protection scheme incorporating setting impedance compensation. The methodology involves: firstly, real-time computation of system sequence impedances to derive the composite equivalent impedance; secondly implementation of a compensation impedance, calculated as the difference between the original positive-sequence impedance and the equivalent composite impedance during phase-to-phase short-circuit conditions; and thirdly imposition of a security constraint ensuring the modified setting impedance remains below the total line impedance to prevent maloperation. Extensive Simulink simulations validate the proposed method’s efficacy, demonstrating both reliable operation for phase-to-phase faults at the transmission outlet of synchronous condenser-wind farm systems and significantly improved tolerance to fault resistance effects.
Authors
- Baohua Wang (ORCID: https://orcid.org/0000-0001-6327-2626)
- Guowen Sun (ORCID: https://orcid.org/0009-0000-7064-3456)
Institutions
- Nanjing University of Science and Technology (CN)
Publication Details
- Published
- 2025-08-15
- DOI
- https://doi.org/10.1109/iccepe66357.2025.11192854
- Primary Topic
- Power Systems Fault Detection
- Type
- article
- Field-Weighted Citation Impact
- 0.00