Research on Dynamic Simulation and Optimization of Building Energy Consumption of Substations in Cold Regions Based on DeST: A Case Study of an Indoor Substation in Shijiazhuang
Against the backdrop of the global energy crisis and the “dual carbon” goals (carbon peaking and carbon neutrality), the passive energy-saving design of substation buildings in cold regions faces severe challenges. This study systematically conducts a decomposed analysis of the shape coefficient, thermal performance of the building envelope (including external walls, internal walls, roofs, and external windows), and window-to-wall ratio of substation buildings in cold regions, quantifies the degree of influence of each factor, and proposes corresponding energy-saving design strategies. This study took a 110 kV substation in Yuhua District, Shijiazhuang City, Hebei Province, as the research object. A building energy consumption model was established based on DeST (2023) software, and the influence of the building shape coefficient, U-values of the envelope structure (external walls, internal walls, roofs, external windows), and window-to-wall ratio on the building’s cooling and heating loads was analyzed using the numerical simulation and control variable methods. Leveraging a rigorously validated, high-resolution simulation framework, we quantitatively dissect the marginal energy penalties and payoffs of every passive design variable governing fully indoor substations in cold-climate zones. The resultant multidimensional response surfaces are distilled into a deterministic, climate-specific passive energy-saving protocol that secures heating-energy savings of up to 43% without compromising electrical safety or operational accessibility. (1) Reducing the shape coefficient can significantly lower the heat load, and it is recommended to control it at 0.35–0.40; (2) The thermal performance of the envelope structure has a differential effect: the energy-saving effect is optimal when the U-value of external walls is 0.20–0.30 W/(m2·K) and the U-value of roofs is ≤0.25 W/(m2·K). A U-value of 2.4 W/(m2·K) is recommended for external windows, while the internal wall exerts a weak influence; (3) The window-to-wall ratio should be controlled by orientation: east-facing/north-facing ≤ 0.20, south-facing ≤ 0.35, and west-facing ≤ 0.30. Based on the above results, a comprehensive energy-saving strategy of “compact form–high-efficiency envelope–limited window-to-wall ratio” is proposed, which provides theoretical support and technical pathways for the energy-saving design of substation buildings in cold areas. Compared with existing substation buildings, the recommended parameters yield a significant reduction in total life-cycle carbon emissions and hold important practical significance for realizing the “dual carbon” goals (carbon peaking and carbon neutrality) of the power system.
Authors
- Ligai Kang (ORCID: https://orcid.org/0000-0003-3120-2660)
- Lingzhe Zhang (ORCID: https://orcid.org/0009-0005-9500-4489)
- Jizhi Su
- Jun Zhang (ORCID: https://orcid.org/0000-0002-6666-8703)
- Jiaming Wang (ORCID: https://orcid.org/0000-0003-3631-5728)
- Xu Zhang
- Haifeng Yu
- Wuchen Zhang
Institutions
- Hebei University of Science and Technology (CN)
- Economic Research Institute (BG)
- Hebei Science and Technology Department (CN)
Publication Details
- Journal
- Buildings
- Published
- 2025-10-15
- DOI
- https://doi.org/10.3390/buildings15203706
- Citations
- 1
- Primary Topic
- Underground infrastructure and sustainability
- Type
- article
- Field-Weighted Citation Impact
- 1.01