Research on coverage optimization and verification of oil depot fire and gas system detectors based on Effigy software
To address monitoring blind zones in oil depot Fire & Gas System (FGS) detector layouts, this study proposes a performance-based optimization methodology compliant with ISA 84.00.07 standards. Targeting a refined oil depot, we constructed a 3D risk model using Effigy software integrated with DNV Safeti gas dispersion data to quantitatively evaluate detector coverage and optimize layout. Results demonstrate: Initial gas detector coverage was merely 57.4%. Through deployment of 5 additional gas detectors and 3 flame detectors, overall coverage increased to 95.8%, reducing residual risk to 4.3×10<sup>-4</sup>/year. This methodology provides technical support for high-reliability FGS design.
Authors
- Zhijun Jin (ORCID: https://orcid.org/0000-0001-9739-981X)
- Xuefeng Han (ORCID: https://orcid.org/0000-0002-9858-8003)
- Yang Cao (ORCID: https://orcid.org/0000-0003-3111-5751)
Institutions
- Nanjing Tech University (CN)
Publication Details
- Published
- 2025-10-14
- DOI
- https://doi.org/10.1117/12.3088699
- Primary Topic
- Risk and Safety Analysis
- Type
- article
- Field-Weighted Citation Impact
- 0.00