Parametric analysis of overvoltage phenomenon during single-phase to earth faults in medium-voltage grids

Because of the more frequent use of underground cables, the capacitive current in medium-voltage power substations is getting higher and when associated to other grid characteristics, it can be the origin of high overvoltage levels during single-phase to earth faults, which can be observed in the entire grid in the two healthy phases. This paper has the objective of demonstrating that four grid parameters have an important impact in overvoltage levels in this particular context: grounding systems, capacitive currents, short-circuit power of the upstream grid and the fault impedance. Through a hybrid steady-state and transient analysis, two parametric studies were conducted. These analyses allow to conclude that in terms of grounding system, the ones creating the higher levels of overvoltage are the ones where the grounding impedance is high, such as impedance-based grounding and compensated grounding in under-compensation mode. It is also possible to infer that the combination of high capacitive currents and low short-circuit impedance of the upstream HV grid can be the source of high overvoltage. At last, it is possible to observe that once the fault impedance is high enough it becomes the principal limiting factor for the voltage level of non-faulty phases.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.1895
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Parametric analysis of overvoltage phenomenon during single-phase to earth faults in medium-voltage grids

César Augusto Slongo, Benjamin Schuler, J. Sánchez, Dumitru Mecineanu
IET conference proceedings.
Power Systems Fault Detection
article

Parametric analysis of overvoltage phenomenon during single-phase to earth faults in medium-voltage grids

César Augusto Slongo, Benjamin Schuler, J. Sánchez, Dumitru Mecineanu
article en

Abstract

Because of the more frequent use of underground cables, the capacitive current in medium-voltage power substations is getting higher and when associated to other grid characteristics, it can be the origin of high overvoltage levels during single-phase to earth faults, which can be observed in the entire grid in the two healthy phases. This paper has the objective of demonstrating that four grid parameters have an important impact in overvoltage levels in this particular context: grounding systems, capacitive currents, short-circuit power of the upstream grid and the fault impedance. Through a hybrid steady-state and transient analysis, two parametric studies were conducted. These analyses allow to conclude that in terms of grounding system, the ones creating the higher levels of overvoltage are the ones where the grounding impedance is high, such as impedance-based grounding and compensated grounding in under-compensation mode. It is also possible to infer that the combination of high capacitive currents and low short-circuit impedance of the upstream HV grid can be the source of high overvoltage. At last, it is possible to observe that once the fault impedance is high enough it becomes the principal limiting factor for the voltage level of non-faulty phases.

IET conference proceedings.Vol. 2025(14)
Direction de la Recherche Technologique (FR), Électricité de France (France) (FR)
Openalex Percentile: Top 63%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Parametric analysis of overvoltage phenomenon during single-phase to earth faults in medium-voltage grids — César Augusto Slongo, Benjamin Schuler, et al. · IET conference proceedings. (2025) | TGRS Research Map | TGRS