Reducing the data size of supraharmonic measurements to verify EMC compliance
For decades, power quality (PQ) data required large storage, typically 40-50 harmonic orders per channel, measured weekly. With the rise of supraharmonics, instruments now store up to 57 times more data. This paper presents a histogram-based method to reduce data storage by a factor of 533 for long-term monitoring and a benchmarkingPQat the utility-customer connection. Referencing IEC EMC coordination, the method provides equations for calculating supraharmonic compatibility and planning levels. It was applied at a metalworking shop where LED luminaires are damaged by supraharmonics every 3 months.
Authors
- Daniel Massicotte (ORCID: https://orcid.org/0000-0002-7807-7919)
- R. Bergeron (ORCID: https://orcid.org/0009-0005-5827-3305)
- Manouane Caza-Szoka (ORCID: https://orcid.org/0000-0001-7828-6166)
- Philippe Blanchard (ORCID: https://orcid.org/0009-0009-4429-9685)
Institutions
- Université du Québec à Trois-Rivières (CA)
Publication Details
- Journal
- IET conference proceedings.
- Published
- 2025-10-14
- DOI
- https://doi.org/10.1049/icp.2025.1486
- Primary Topic
- Power Line Communications and Noise
- Type
- article
- Field-Weighted Citation Impact
- 0.00