New method for step and touch voltages verification by continuous loop impedance monitoring

This paper outlines a strategy for monitoring earth loop impedance and ensuring compliance with step and touch voltage limits in distribution networks using insulated cables with monitoring systems. These voltages, regulated by EN 50522 [1] and national laws such as Spain's Royal Decree 337/2014 [2], must be measured during commissioning tests and verified periodically. In medium-voltage (MV) networks of up to 36 kV, step and touch voltage measurements can be replaced by earth resistance measurements if a validated correlation exists. Loop impedance measurements, conducted with current injectors (frequencies < 2 kHz), allow the estimation of the earth resistance of transformer station (connected through insulated cables. Compliance with step and touch voltages strongly depends on the fault current distribution at each transformer station, influenced by the earth resistances of other interconnected stations. Using the current distribution coefficient (α), various scenarios of network topology and neutral earthing systems are analysed. The objective is to correlate the loop impedance with a fault current distribution coefficient, enabling the estimation of confident upper limits for step and touch voltages, thereby verifying compliance with safety voltage requirements in distribution networks [2], [3],[4].

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.2114
Primary Topic
Advanced Electrical Measurement Techniques
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

New method for step and touch voltages verification by continuous loop impedance monitoring

Pascual Simón, José R. Vidal, Abderrahim Khamlichi, Asier Vicente et al.
IET conference proceedings.
Advanced Electrical Measurement Techniques
article

New method for step and touch voltages verification by continuous loop impedance monitoring

Pascual Simón, José R. Vidal, Abderrahim Khamlichi, Asier Vicente, Jorge Rovira, Antonio González, J.L. Navarro
article en

Abstract

This paper outlines a strategy for monitoring earth loop impedance and ensuring compliance with step and touch voltage limits in distribution networks using insulated cables with monitoring systems. These voltages, regulated by EN 50522 [1] and national laws such as Spain's Royal Decree 337/2014 [2], must be measured during commissioning tests and verified periodically. In medium-voltage (MV) networks of up to 36 kV, step and touch voltage measurements can be replaced by earth resistance measurements if a validated correlation exists. Loop impedance measurements, conducted with current injectors (frequencies < 2 kHz), allow the estimation of the earth resistance of transformer station (connected through insulated cables. Compliance with step and touch voltages strongly depends on the fault current distribution at each transformer station, influenced by the earth resistances of other interconnected stations. Using the current distribution coefficient (α), various scenarios of network topology and neutral earthing systems are analysed. The objective is to correlate the loop impedance with a fault current distribution coefficient, enabling the estimation of confident upper limits for step and touch voltages, thereby verifying compliance with safety voltage requirements in distribution networks [2], [3],[4].

IET conference proceedings.Vol. 2025(14)
Equipos Nucleares (Spain) (ES), Fundación para el Fomento de la Innovación Industrial (ES), Gas Natural Fenosa (Spain) (ES), Grupo ACS (Spain) (ES)
Openalex Percentile: Top 71%
Advanced Electrical Measurement Techniques
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.