Application limits for transient earth-fault analysis of symmetrical components in compensated grids under unbalanced conditions

Unbalanced grids may have variations in line and coupling impedances, as well as capacitances, requiring further considerations for symmetrical component calculations. This leads to deviations between the symmetrical component model and reality. These deviations are demonstrated on a medium-voltage grid and their respective values are determined. Due to the unbalance, a zero-sequence voltage occurs which varies with the grid conditions. Alternative methods of balancing the grid to reduce unbalances are analysed. Cable shield currents must be determined separately, as they are not directly obtained using symmetrical components. The impact of grid unbalances on the transient behavior during earth-fault initiation and clearing is also studied.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.1719
Primary Topic
Power Systems and Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Application limits for transient earth-fault analysis of symmetrical components in compensated grids under unbalanced conditions

Lothar Fickert, Matthias Robeischl, Peter Dopplmair
IET conference proceedings.
Power Systems and Technologies
article

Application limits for transient earth-fault analysis of symmetrical components in compensated grids under unbalanced conditions

Lothar Fickert, Matthias Robeischl, Peter Dopplmair
article en

Abstract

Unbalanced grids may have variations in line and coupling impedances, as well as capacitances, requiring further considerations for symmetrical component calculations. This leads to deviations between the symmetrical component model and reality. These deviations are demonstrated on a medium-voltage grid and their respective values are determined. Due to the unbalance, a zero-sequence voltage occurs which varies with the grid conditions. Alternative methods of balancing the grid to reduce unbalances are analysed. Cable shield currents must be determined separately, as they are not directly obtained using symmetrical components. The impact of grid unbalances on the transient behavior during earth-fault initiation and clearing is also studied.

IET conference proceedings.Vol. 2025(14)
Graz University of Technology (AT)
Openalex Percentile: Top 71%
Power Systems and Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.