Effects of system contacts between 400 kV and 110 kV systems in transmission and distribution networks

New 110 kV and 400 kV overhead lines are often installed on a line tower. Contact between the systems leads to large overvoltages in the 110 kV system and may not be reliably detected by the protection devices. Based on real faults, the paper shows the consequences of system contact between a 400 kV and a 110 kV overhead line. Fault records and equipment failures in the networks involved are analysed. Analytical calculation methods based on symmetrical components are presented to estimate the maximum overvoltages. Theoretical considerations are complemented by simulation calculations. The effects on the insulation co-ordination of the equipment are shown.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.1911
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effects of system contacts between 400 kV and 110 kV systems in transmission and distribution networks

Uwe Schmidt, Sofia Hauschild, Martin Schulze, J. Haensch et al.
IET conference proceedings.
Power Systems Fault Detection
article

Effects of system contacts between 400 kV and 110 kV systems in transmission and distribution networks

Uwe Schmidt, Sofia Hauschild, Martin Schulze, J. Haensch, D. Watschinski
article en

Abstract

New 110 kV and 400 kV overhead lines are often installed on a line tower. Contact between the systems leads to large overvoltages in the 110 kV system and may not be reliably detected by the protection devices. Based on real faults, the paper shows the consequences of system contact between a 400 kV and a 110 kV overhead line. Fault records and equipment failures in the networks involved are analysed. Analytical calculation methods based on symmetrical components are presented to estimate the maximum overvoltages. Theoretical considerations are complemented by simulation calculations. The effects on the insulation co-ordination of the equipment are shown.

IET conference proceedings.Vol. 2025(14)
Amprion (United States) (US), Zittau/Görlitz University of Applied Sciences (DE), Internationales Institut für Nachhaltiges Energiemanagement, Politik, Risiko und Soziale Innovationen (DE), BH Consulting (Ireland) (IE)
Openalex Percentile: Top 63%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.