Passive filter design for weak distribution system with 24-pulse converter load using EMT models

The article deal with harmonic distortion in distribution network because of a huge 2 x 5.5 MW load (motors) is supplied by 24-pulse rectifier, dc line and convertor. The EMT model of the network for harmonic distortion evaluation was assembled. Values of THD, TDD and individual harmonic content were computed, and the results were compared with technical standards (IEEE-519-2022 and IEC/TR 61000-3-6.). Some configurations of distribution network with underground cables and overhead lines were tested and the worst cases were found. The evaluations of EMT computation results of that cases according to standards lead to a decision for passive filter installations. The further investigation was focused to find proper passive filter scheme, and parameters of RLC elements. The aim of investigation is the best filters efficiency to mitigate harmonics with minimum of reactive power consumption and power losses for the fundamental harmonic component (50 Hz). Some types of filters and its combinations were designed and tested in EMTP models with the aim to find the best of them.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.1509
Primary Topic
Power Line Communications and Noise
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Passive filter design for weak distribution system with 24-pulse converter load using EMT models

Martin Švancar
IET conference proceedings.
Power Line Communications and Noise
article

Passive filter design for weak distribution system with 24-pulse converter load using EMT models

Martin Švancar
article en

Abstract

The article deal with harmonic distortion in distribution network because of a huge 2 x 5.5 MW load (motors) is supplied by 24-pulse rectifier, dc line and convertor. The EMT model of the network for harmonic distortion evaluation was assembled. Values of THD, TDD and individual harmonic content were computed, and the results were compared with technical standards (IEEE-519-2022 and IEC/TR 61000-3-6.). Some configurations of distribution network with underground cables and overhead lines were tested and the worst cases were found. The evaluations of EMT computation results of that cases according to standards lead to a decision for passive filter installations. The further investigation was focused to find proper passive filter scheme, and parameters of RLC elements. The aim of investigation is the best filters efficiency to mitigate harmonics with minimum of reactive power consumption and power losses for the fundamental harmonic component (50 Hz). Some types of filters and its combinations were designed and tested in EMTP models with the aim to find the best of them.

IET conference proceedings.Vol. 2025(14)
EGU HV Laboratory (CZ)
Openalex Percentile: Top 71%
Power Line Communications and Noise
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.