Boston SPA energy efficiency trial - a novel method to implement conservation voltage reduction

The Boston Spa Energy Efficiency Trial (BEET) uses smart meter voltage measurements to control the 11kV system voltage at two 33/11kV (primary) substations supplying circa 15,000 customers in Yorkshire, Great Britain. The voltage on the low voltage (LV) network is normally operated towards the high end of statutory limits (216.2 – 253.0V) in order to account for the voltage drop on the network under winter peak demand conditions and/or during network outages. By taking voltage measurements from smart meters located at LV customers’ points of supply it is possible to regulate the 11kV system voltage in near real time in order to lower customers’ LV supply voltage. The key benefits are conservation voltage reduction (CVR) and providing the opportunity to connect additional demand and generation without going beyond statutory limits. BEET provides a novel way to implement CVR without the need for capital expenditure on 11kV/LV on-load tap changing transformers or LV voltage regulators. It also provides immediate bill reductions and carbon savings to customers whether they have a smart meter installed or not. BEET provides new learning on the retrieval and use of smart meter voltage data in real-time.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.1733
Primary Topic
Energy Efficiency and Management
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Boston SPA energy efficiency trial - a novel method to implement conservation voltage reduction

Vincent Thornley, Susan Morgan, F. Shillitoe, Steve Webb et al.
IET conference proceedings.
Energy Efficiency and Management
article

Boston SPA energy efficiency trial - a novel method to implement conservation voltage reduction

Vincent Thornley, Susan Morgan, F. Shillitoe, Steve Webb, Keith Jackson, Mark Callum, Roger Lynn
article en

Abstract

The Boston Spa Energy Efficiency Trial (BEET) uses smart meter voltage measurements to control the 11kV system voltage at two 33/11kV (primary) substations supplying circa 15,000 customers in Yorkshire, Great Britain. The voltage on the low voltage (LV) network is normally operated towards the high end of statutory limits (216.2 – 253.0V) in order to account for the voltage drop on the network under winter peak demand conditions and/or during network outages. By taking voltage measurements from smart meters located at LV customers’ points of supply it is possible to regulate the 11kV system voltage in near real time in order to lower customers’ LV supply voltage. The key benefits are conservation voltage reduction (CVR) and providing the opportunity to connect additional demand and generation without going beyond statutory limits. BEET provides a novel way to implement CVR without the need for capital expenditure on 11kV/LV on-load tap changing transformers or LV voltage regulators. It also provides immediate bill reductions and carbon savings to customers whether they have a smart meter installed or not. BEET provides new learning on the retrieval and use of smart meter voltage data in real-time.

IET conference proceedings.Vol. 2025(14)
UK Research and Innovation (GB), Film Independent (US), Northern Powergrid (United Kingdom) (GB), Oldham Council (GB), Newcastle University (GB)
Openalex Percentile: Top 80%
Energy Efficiency and Management
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Boston SPA energy efficiency trial - a novel method to implement conservation voltage reduction — Vincent Thornley, Susan Morgan, et al. · IET conference proceedings. (2025) | TGRS Research Map | TGRS