New improved method for measuring the earthfault-distance in non-solid grounded networks

Current earth fault distance measurement based on symmetrical components does not work very well in compensated systems because the steady-state currents through the fault location are significantly smaller than the load currents. It is not possible to distinguish between load current and fault current. It has also been assumed that the fault impedance, including the arc, is a linear impedance. However, this is not the case in the real world, especially for faults in the cable section of a line. The air gap creates an additional layer of insulation with increased and variable ignition voltage. This non-linearity affects the current waveform, voltage waveform, and frequency of the low-current arc. With the new modified method, it is now possible to distinguish between the fault current and the load current and to compensate for the effects of the nonlinearities of the fault impedances. The accuracy of the impedance measurement from the measuring point to the fault location is significantly improved. This paper presents the new method in detail for self-extinguishing and re-igniting earth faults in overhead and cable networks.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2025-10-14
DOI
https://doi.org/10.1049/icp.2025.2241
Primary Topic
Geophysical Methods and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

New improved method for measuring the earthfault-distance in non-solid grounded networks

Robert Steinbichler, Christian Freund, Jörg Meyer, Peter Schegner et al.
IET conference proceedings.
Geophysical Methods and Applications
article

New improved method for measuring the earthfault-distance in non-solid grounded networks

Robert Steinbichler, Christian Freund, Jörg Meyer, Peter Schegner, Oliver Skrbinjek, Gernot Druml, Thomas Schinerl, Bruno Wartmann
article en

Abstract

Current earth fault distance measurement based on symmetrical components does not work very well in compensated systems because the steady-state currents through the fault location are significantly smaller than the load currents. It is not possible to distinguish between load current and fault current. It has also been assumed that the fault impedance, including the arc, is a linear impedance. However, this is not the case in the real world, especially for faults in the cable section of a line. The air gap creates an additional layer of insulation with increased and variable ignition voltage. This non-linearity affects the current waveform, voltage waveform, and frequency of the low-current arc. With the new modified method, it is now possible to distinguish between the fault current and the load current and to compensate for the effects of the nonlinearities of the fault impedances. The accuracy of the impedance measurement from the measuring point to the fault location is significantly improved. This paper presents the new method in detail for self-extinguishing and re-igniting earth faults in overhead and cable networks.

IET conference proceedings.Vol. 2025(14)
University of Education Upper Austria (AT), University of Teacher Education Styria (AT), Amt für Städtebau (CH), Institute of Automation (DE), Hochschule für Technik und Wirtschaft Dresden – University of Applied Sciences (DE), Technische Universität Dresden (DE)
Openalex Percentile: Top 64%
Geophysical Methods and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

New improved method for measuring the earthfault-distance in non-solid grounded networks — Robert Steinbichler, Christian Freund, et al. · IET conference proceedings. (2025) | TGRS Research Map | TGRS