Energy, exergy, and environmental analysis of five low-GWP refrigerants considered as alternatives to R410A for air conditioning systems

Abstract The sustainability concern of high Global Warming Potential (GWP) refrigerants like R410A has spurred universal efforts in searching for low-GWP replacements in vapor-compression air conditioning systems. This study undertakes a comprehensive energy, exergy, and environmental analysis of five low-GWP refrigerants R32, R290, R454B, R454C, and R513A to be used as alternatives to R410A. A model of a single-stage vapor compression cycle was constructed and simulated with Engineering Equation Solver (EES) with real fluid property data under steady-state conditions. Simulation was undertaken using evaporating temperatures of –5 °C to 5 °C and condensing temperatures of 30 °C to 50 °C with fixed subcooling (5 K) and superheat (7 K) values. To maintain accuracy and credibility, the model was checked against literature data of experiments under similar working conditions with deviation of less than 10% in mass flow rate, discharge temperature, cooling capacity, power to compressor, and Coefficient of Performance (COP). From the analysis, it is found that R290 has the best thermodynamic performance with an optimal COP value of 7.91, 5.6% better than R410A and an optimal cooling capacity of 4.30 kW, 19.3% greater than R410A. It achieves the highest exergy efficiency of 0.52 and the lowest exergy destruction in components. R454B, with slightly lower COP performance, has the lowest Total Equivalent Warming Impact (TEWI) of 13.3 tons CO₂, which is some 16% less than R410A. On the other hand, R454C has the highest exergy destruction of 120.4 W and TEWI of 18.4 tons CO₂. R290 and R454B are thus found to be the best low-GWP options to fulfill the transition to environment-friendly and energy-efficient air conditioning systems.

Authors

Institutions

Publication Details

Journal
International Journal of Air-Conditioning and Refrigeration
Published
2025-10-09
DOI
https://doi.org/10.1007/s44189-025-00087-x
Citations
6
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
4.28
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Energy, exergy, and environmental analysis of five low-GWP refrigerants considered as alternatives to R410A for air conditioning systems

Saif Ali Kadhim, Ravishankar Sathyamurthy, Hayder Mohsin Ali, Abdallah Bouabidi et al.
6 citations
International Journal of Air-Conditioning and Refrigeration
Refrigeration and Air Conditioning Technologies
4.28
article

Energy, exergy, and environmental analysis of five low-GWP refrigerants considered as alternatives to R410A for air conditioning systems

Saif Ali Kadhim, Ravishankar Sathyamurthy, Hayder Mohsin Ali, Abdallah Bouabidi, Karrar Abed Hammoodi, Farhan Lafta Rashid, Ali M. Ashour
article en
6 citations

Abstract

Abstract The sustainability concern of high Global Warming Potential (GWP) refrigerants like R410A has spurred universal efforts in searching for low-GWP replacements in vapor-compression air conditioning systems. This study undertakes a comprehensive energy, exergy, and environmental analysis of five low-GWP refrigerants R32, R290, R454B, R454C, and R513A to be used as alternatives to R410A. A model of a single-stage vapor compression cycle was constructed and simulated with Engineering Equation Solver (EES) with real fluid property data under steady-state conditions. Simulation was undertaken using evaporating temperatures of –5 °C to 5 °C and condensing temperatures of 30 °C to 50 °C with fixed subcooling (5 K) and superheat (7 K) values. To maintain accuracy and credibility, the model was checked against literature data of experiments under similar working conditions with deviation of less than 10% in mass flow rate, discharge temperature, cooling capacity, power to compressor, and Coefficient of Performance (COP). From the analysis, it is found that R290 has the best thermodynamic performance with an optimal COP value of 7.91, 5.6% better than R410A and an optimal cooling capacity of 4.30 kW, 19.3% greater than R410A. It achieves the highest exergy efficiency of 0.52 and the lowest exergy destruction in components. R454B, with slightly lower COP performance, has the lowest Total Equivalent Warming Impact (TEWI) of 13.3 tons CO₂, which is some 16% less than R410A. On the other hand, R454C has the highest exergy destruction of 120.4 W and TEWI of 18.4 tons CO₂. R290 and R454B are thus found to be the best low-GWP options to fulfill the transition to environment-friendly and energy-efficient air conditioning systems.

International Journal of Air-Conditioning and RefrigerationVol. 33(1)
King Fahd University of Petroleum and Minerals (SA), University of Technology - Iraq (IQ), University of Al Maarif (IQ), University of Kerbala (IQ), University of Gabès (TN)
Openalex Percentile: Top 5%
Refrigeration and Air Conditioning Technologies
4.28
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.