Constrained angle control in power grids comprising virtual synchronous machines

In order to ensure synchronism in a power grid, the relative electric angles of the (virtual) synchronous generators in this grid must remain close to a desired stable equilibrium point, which implies that these angles should remain small. In particular, asynchronous rotations must be avoided, as they may cause the protections to disconnect generators and may even lead to a breakdown of the system. This can happen as the result of a fault, when the grid impedances between the individual machines become too large, so that the coupling between generators may become too weak. Maintaining synchronism is a classical and well studied problem in power systems, but the emergence of power systems comprising inverters operated as virtual synchronous machines (VSMs) opens up new horizons. Most importantly, such VSMs will be embedded in modern communication infrastructures, such that a real time exchange of information between individual machines becomes conceivable. In such systems we may apply control techniques that are not feasible for traditional generators, such as instantaneous frequency droop and virtual friction. Here we propose to apply constrained control inspired by projected dynamical systems theory, to limit the allowed deviation of the relative angles of VSMs, thus preventing asynchronous rotations, and helping the power grid to more easily recover after a large disturbance.

Authors

Institutions

Publication Details

Published
2025-06-29
DOI
https://doi.org/10.1109/powertech59965.2025.11180437
Primary Topic
Distributed and Parallel Computing Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Constrained angle control in power grids comprising virtual synchronous machines

George H. Weiss, Florian Reißner
Distributed and Parallel Computing Systems
article

Constrained angle control in power grids comprising virtual synchronous machines

George H. Weiss, Florian Reißner
article en

Abstract

In order to ensure synchronism in a power grid, the relative electric angles of the (virtual) synchronous generators in this grid must remain close to a desired stable equilibrium point, which implies that these angles should remain small. In particular, asynchronous rotations must be avoided, as they may cause the protections to disconnect generators and may even lead to a breakdown of the system. This can happen as the result of a fault, when the grid impedances between the individual machines become too large, so that the coupling between generators may become too weak. Maintaining synchronism is a classical and well studied problem in power systems, but the emergence of power systems comprising inverters operated as virtual synchronous machines (VSMs) opens up new horizons. Most importantly, such VSMs will be embedded in modern communication infrastructures, such that a real time exchange of information between individual machines becomes conceivable. In such systems we may apply control techniques that are not feasible for traditional generators, such as instantaneous frequency droop and virtual friction. Here we propose to apply constrained control inspired by projected dynamical systems theory, to limit the allowed deviation of the relative angles of VSMs, thus preventing asynchronous rotations, and helping the power grid to more easily recover after a large disturbance.

Tel Aviv University (IL)
Openalex Percentile: Top 67%
Distributed and Parallel Computing Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.