Stress testing power grids for cascades due to combined cyber and physical attacks
Due to the growing deployment of weakly protected Internet-of-Things devices connected to power grids, the probability and possible magnitude of cyber-induced load-altering attacks increases. At the same time, cascading failures in power grids can amplify the effect of a few initial line failures such that large blackouts occur. This paper aims to quantify the possible loss of load realizable by an omniscient adversary using combined load-altering and line interdiction attacks, exploiting cascading processes and accounting for system operators’ possible remedial actions. The resulting multi-stage bilevel optimization problem is transformed into a tractable single-level problem that can be solved by common MILP-solvers. Two case studies for the WSC C 9-Bus and IEEE RTS 24-Bus systems reveal that even N-1 secure system operation is not sufficient to avoid loss of load under potential load-altering attacks and that ignoring cascades underestimates the potential impact of such attacks.
Authors
- Florian Steinke (ORCID: https://orcid.org/0000-0003-3012-9991)
- Kirill Kuroptev
Institutions
- Technische Universität Darmstadt (DE)
Publication Details
- Published
- 2025-06-29
- DOI
- https://doi.org/10.1109/powertech59965.2025.11180452
- Primary Topic
- Smart Grid Security and Resilience
- Type
- article
- Field-Weighted Citation Impact
- 0.00