Enhanced thermal management and energy efficiency in electronic processor cooling using MWCNT-LA NEPCM heat sink with U-tube heat pipes

This study investigates the efficiency of a multi-walled carbon nanotube-infused lauric acid (MWCNT-LA) heatsink with U-tube heat pipes filled with n-pentane for electronic processor cooling. Experimental evaluations were conducted under varying heat loads and filling ratios to assess processor stability and energy efficiency. The investigation focused on energy savings, the thermal resistance of different heat pipe-assisted heatsink modules with multi-walled carbon nanotube-infused lauric acid phase change material, with its regeneration time, and optimal heat pipe filling ratio. Results showed that the MWCNT-LA heat sink module with 50% n-pentane filling performed best under higher heat loads, achieving the lowest thermal resistance of 0.63 °C/W at 50% filling ratio and 75% heat load. This design was 3.58 times more effective than the unfilled heat pipe version and achieved 78% energy savings with minimal cooling fan energy consumption. The developed heat sink design improves thermal management by utilizing latent heat storage and enhancing heat transport efficiency through the heat pipe, thus optimizing thermal performance, heat dissipation, and temperature regulation. These improvements increased the operational reliability and energy efficiency of processors in data center cooling applications. • Multi-walled carbon nanotubes embedded in lauric acid phase change material. • Nano-embedded phase change material-filled finned heat sink. • Nano-embedded phase change material heat sink increases operating time by 3.58 times. • Lower thermal resistance of 0.63 °C•W −1 at 50% filling ratio and 75% heat load. • Fifty percent is the optimum filling ratio for U-tube heat pipe.

Authors

Publication Details

Journal
Next Energy
Published
2025-10-01
DOI
https://doi.org/10.1016/j.nxener.2025.100440
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Enhanced thermal management and energy efficiency in electronic processor cooling using MWCNT-LA NEPCM heat sink with U-tube heat pipes

A. Lakshmi Kanthan Bharathi, S. Kalaiselvam, A. Ameelia Roseline
Next Energy
Heat Transfer and Optimization
article

Enhanced thermal management and energy efficiency in electronic processor cooling using MWCNT-LA NEPCM heat sink with U-tube heat pipes

A. Lakshmi Kanthan Bharathi, S. Kalaiselvam, A. Ameelia Roseline
article en

Abstract

This study investigates the efficiency of a multi-walled carbon nanotube-infused lauric acid (MWCNT-LA) heatsink with U-tube heat pipes filled with n-pentane for electronic processor cooling. Experimental evaluations were conducted under varying heat loads and filling ratios to assess processor stability and energy efficiency. The investigation focused on energy savings, the thermal resistance of different heat pipe-assisted heatsink modules with multi-walled carbon nanotube-infused lauric acid phase change material, with its regeneration time, and optimal heat pipe filling ratio. Results showed that the MWCNT-LA heat sink module with 50% n-pentane filling performed best under higher heat loads, achieving the lowest thermal resistance of 0.63 °C/W at 50% filling ratio and 75% heat load. This design was 3.58 times more effective than the unfilled heat pipe version and achieved 78% energy savings with minimal cooling fan energy consumption. The developed heat sink design improves thermal management by utilizing latent heat storage and enhancing heat transport efficiency through the heat pipe, thus optimizing thermal performance, heat dissipation, and temperature regulation. These improvements increased the operational reliability and energy efficiency of processors in data center cooling applications. • Multi-walled carbon nanotubes embedded in lauric acid phase change material. • Nano-embedded phase change material-filled finned heat sink. • Nano-embedded phase change material heat sink increases operating time by 3.58 times. • Lower thermal resistance of 0.63 °C•W −1 at 50% filling ratio and 75% heat load. • Fifty percent is the optimum filling ratio for U-tube heat pipe.

Next EnergyVol. 9
Openalex Percentile: Top 72%
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Enhanced thermal management and energy efficiency in electronic processor cooling using MWCNT-LA NEPCM heat sink with U-tube heat pipes — A. Lakshmi Kanthan Bharathi, S. Kalaiselvam, et al. · Next Energy (2025) | TGRS Research Map | TGRS