Abstract The ban on the use of the greenhouse gas SF 6 as an insulating and extinguishing gas in equipment and switchgear under the EU’s F‑Gas Regulation requires the use of alternative technologies. This article shows the findings of short-cicuit and operational switching tests of the first installed vacuum circuit breaker in the 110-kV grid in Austria. The focus is to assess the performance during the switching operations and the discussion of the occurred phenomena. Transient phenomena can only be recorded with the use of high-bandwidth CR dividers for voltage and fiber-optic sensors for current measurement. The article investigates a symmetrical terminal fault with multiple reignitions in detail and discusses the switching of a no-loaded transformer. All operational switchings including fault clearings are standard conform and offer valuable insights into the dynamic response of the grid. As result the circuit breaker has been successfully commissioned and is now in operation in the 110-kV coupling bay.

Authors

Institutions

Publication Details

Journal
e+i Elektrotechnik und Informationstechnik
Published
2025-09-24
DOI
https://doi.org/10.1007/s00502-025-01335-z
Primary Topic
Vacuum and Plasma Arcs
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Field tests of a vacuum circuit breaker in the 110-kV high voltage grid

Robert Schürhuber, Philipp Hackl, Lukas Schwalt, Maximilian Heinz Brestan
e+i Elektrotechnik und Informationstechnik
Vacuum and Plasma Arcs
article

Field tests of a vacuum circuit breaker in the 110-kV high voltage grid

Robert Schürhuber, Philipp Hackl, Lukas Schwalt, Maximilian Heinz Brestan
article en

Abstract

Abstract The ban on the use of the greenhouse gas SF 6 as an insulating and extinguishing gas in equipment and switchgear under the EU’s F‑Gas Regulation requires the use of alternative technologies. This article shows the findings of short-cicuit and operational switching tests of the first installed vacuum circuit breaker in the 110-kV grid in Austria. The focus is to assess the performance during the switching operations and the discussion of the occurred phenomena. Transient phenomena can only be recorded with the use of high-bandwidth CR dividers for voltage and fiber-optic sensors for current measurement. The article investigates a symmetrical terminal fault with multiple reignitions in detail and discusses the switching of a no-loaded transformer. All operational switchings including fault clearings are standard conform and offer valuable insights into the dynamic response of the grid. As result the circuit breaker has been successfully commissioned and is now in operation in the 110-kV coupling bay.

e+i Elektrotechnik und InformationstechnikVol. 142(7-8)
Graz University of Technology (AT), Austrian Energy Agency (AT)
Openalex Percentile: Top 79%
Vacuum and Plasma Arcs
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.