The differential protection scheme offers better selectivity and performance than other protection schemes in addressing protection challenges introduced by integrating ac microgrid into conventional distribution system. However, the presence of tapped load causes differences in electrical parameters (at line ends) during steady-state, system transients, and external faults, thereby reducing the selectivity and sensitivity of the differential scheme. Therefore, this work employs superimposed negative sequence current magnitude and superimposed phase current magnitude, provided to different AND logic Gates (with a 1.5 cycle delay) to identify fault and faulty phases in both operating modes of ac microgrid under different network configurations. The superimposed negative sequence current magnitude effectively distinguishes unsymmetrical faults from different switching transients, including tapped load switching, while superimposed phase current magnitude differentiates symmetrical faults from balanced tapped load switching. The proposed differential scheme is implemented in MATLAB simulation and demonstrates high sensitivity by detecting faults up to 600 Ω in grid mode and 500 Ω in islanded mode. It achieves high selectivity by effectively distinguishing faults from balanced/unbalanced tapped load switching and different system transients, with fast fault detection (within 2 cycles). Moreover, it is compared with recent differential schemes to highlight its high selectivity and sensitivity. The scheme is further validated on laboratory-level hardware-in-loop setup using OPAL-RT 4512 controller and GE P40 MiCOM relay for generating trip signal using IEC 61850 GOOSE protocol.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Industrial Informatics
Published
2025-09-20
DOI
https://doi.org/10.1109/tii.2025.3606199
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Novel Differential Fault Detection Strategy for Smart AC Microgrid Incorporating Tapped Loads

Chandan Kishore, Lie Xu, Agustí Egea‐Àlvarez, Rohit Nandi et al.
IEEE Transactions on Industrial Informatics
Power Systems Fault Detection
article

A Novel Differential Fault Detection Strategy for Smart AC Microgrid Incorporating Tapped Loads

Chandan Kishore, Lie Xu, Agustí Egea‐Àlvarez, Rohit Nandi, Manoj Tripathy
article en

Abstract

The differential protection scheme offers better selectivity and performance than other protection schemes in addressing protection challenges introduced by integrating ac microgrid into conventional distribution system. However, the presence of tapped load causes differences in electrical parameters (at line ends) during steady-state, system transients, and external faults, thereby reducing the selectivity and sensitivity of the differential scheme. Therefore, this work employs superimposed negative sequence current magnitude and superimposed phase current magnitude, provided to different AND logic Gates (with a 1.5 cycle delay) to identify fault and faulty phases in both operating modes of ac microgrid under different network configurations. The superimposed negative sequence current magnitude effectively distinguishes unsymmetrical faults from different switching transients, including tapped load switching, while superimposed phase current magnitude differentiates symmetrical faults from balanced tapped load switching. The proposed differential scheme is implemented in MATLAB simulation and demonstrates high sensitivity by detecting faults up to 600 Ω in grid mode and 500 Ω in islanded mode. It achieves high selectivity by effectively distinguishing faults from balanced/unbalanced tapped load switching and different system transients, with fast fault detection (within 2 cycles). Moreover, it is compared with recent differential schemes to highlight its high selectivity and sensitivity. The scheme is further validated on laboratory-level hardware-in-loop setup using OPAL-RT 4512 controller and GE P40 MiCOM relay for generating trip signal using IEC 61850 GOOSE protocol.

IEEE Transactions on Industrial InformaticsVol. 21(12)
Indian Institute of Technology Roorkee (IN), University of Strathclyde (GB)
Openalex Percentile: Top 68%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.