Study on Lightning-Induced Plasma Extinguishing in 10 kV Distribution Network Lines Based on Electronegative Gas Trifluoroiodomethane

Plasma arcs generated by lightning strikes are prone to tripping distribution lines, especially 10 kV lines. To reduce the lightning-induced tripping rate of 10 kV distribution lines and ensure the safe operation of power systems, this paper proposes a same-level double-fracture lightning protection device containing the electronegative gas trifluoroiodomethane (CF3I). A mathematical model of the gas arc-extinguishing process is established based on magnetohydrodynamics. Meanwhile, the mechanism of CF3I in the arc-extinguishing process is analyzed according to its physical and chemical properties, and the arc-extinguishing process is simulated using COMSOL Multiphysics 6.0. The results show that (1) the arc-extinguishing effect is optimal when the horizontal distance of the compression pipeline of the device is 9 mm; (2) under the action of power frequency currents with different initial phases of π/2 and 0, the arc-extinguishing device can extinguish the arc within 800 μs without re-ignition; and (3) in the arc-extinguishing process involving CF3I, the arc can be extinguished within 710 μs, which is 11.2% quicker than that without CF3I. Meanwhile, CF3I can effectively reduce the arc temperature at the initial stage of arc extinguishing, avoiding damage caused by excessive internal compression of the device.

Authors

Institutions

Publication Details

Journal
Plasma
Published
2025-09-19
DOI
https://doi.org/10.3390/plasma8030037
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study on Lightning-Induced Plasma Extinguishing in 10 kV Distribution Network Lines Based on Electronegative Gas Trifluoroiodomethane

Zhipeng Wu, Ping Huang, Tianrui Li, Biao Zhang et al.
Plasma
Lightning and Electromagnetic Phenomena
article

Study on Lightning-Induced Plasma Extinguishing in 10 kV Distribution Network Lines Based on Electronegative Gas Trifluoroiodomethane

Zhipeng Wu, Ping Huang, Tianrui Li, Biao Zhang, Yiyi Zhang, Y. X. Long, Zhenyu Liu
article en

Abstract

Plasma arcs generated by lightning strikes are prone to tripping distribution lines, especially 10 kV lines. To reduce the lightning-induced tripping rate of 10 kV distribution lines and ensure the safe operation of power systems, this paper proposes a same-level double-fracture lightning protection device containing the electronegative gas trifluoroiodomethane (CF3I). A mathematical model of the gas arc-extinguishing process is established based on magnetohydrodynamics. Meanwhile, the mechanism of CF3I in the arc-extinguishing process is analyzed according to its physical and chemical properties, and the arc-extinguishing process is simulated using COMSOL Multiphysics 6.0. The results show that (1) the arc-extinguishing effect is optimal when the horizontal distance of the compression pipeline of the device is 9 mm; (2) under the action of power frequency currents with different initial phases of π/2 and 0, the arc-extinguishing device can extinguish the arc within 800 μs without re-ignition; and (3) in the arc-extinguishing process involving CF3I, the arc can be extinguished within 710 μs, which is 11.2% quicker than that without CF3I. Meanwhile, CF3I can effectively reduce the arc temperature at the initial stage of arc extinguishing, avoiding damage caused by excessive internal compression of the device.

PlasmaVol. 8(3)
Guangxi University (CN), China Southern Power Grid (China) (CN)
Openalex Percentile: Top 82%
Lightning and Electromagnetic Phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Study on Lightning-Induced Plasma Extinguishing in 10 kV Distribution Network Lines Based on Electronegative Gas Trifluoroiodomethane — Zhipeng Wu, Ping Huang, et al. · Plasma (2025) | TGRS Research Map | TGRS