Dielectric Assessment of 11 kV Three-Core XLPE Power Cable during New Substation Commissioning

Assessing the condition of power cables is crucial to ensure they are ready for operation. Neglecting this can lead to significant losses, especially for large industrial users. A key indicator of potential issues is any discrepancy between the dielectric properties measured during commissioning and those specified by the manufacturer, which may suggest that the cables are not yet ready to be installed. To mitigate such risks, the dielectric performance of newly installed 3C 500MMP XLPE cables was evaluated both before and after jointing and termination, prior to commissioning the new main substation. The assessment included Insulation Resistance (IR) and Dielectric Absorption Ratio (DAR) tests, along with continuity and a 24-hour soaking test to verify electrical connectivity and overall performance. The IR and DAR tests yielded results within acceptable ranges, with insulation resistance values exceeding 0.1 GΩ and DAR values above 1.6. Continuity tests confirmed proper jointing and termination, as evidenced by resistance values below 5 Ω. Furthermore, the absence of tripping incidents during the 24-hour soaking period provided additional assurance of the cables’ readiness for energization.

Authors

Publication Details

Journal
Journal of Power and Energy Engineering
Published
2025-01-01
DOI
https://doi.org/10.4236/jpee.2025.139010
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Dielectric Assessment of 11 kV Three-Core XLPE Power Cable during New Substation Commissioning

Mohd Amin Mohd Noh, Sharin Ab Ghani, Mohd Shahril bin Ahmad Khiar, Imran Sutan Chairul
Journal of Power and Energy Engineering
High voltage insulation and dielectric phenomena
article

Dielectric Assessment of 11 kV Three-Core XLPE Power Cable during New Substation Commissioning

Mohd Amin Mohd Noh, Sharin Ab Ghani, Mohd Shahril bin Ahmad Khiar, Imran Sutan Chairul
article en

Abstract

Assessing the condition of power cables is crucial to ensure they are ready for operation. Neglecting this can lead to significant losses, especially for large industrial users. A key indicator of potential issues is any discrepancy between the dielectric properties measured during commissioning and those specified by the manufacturer, which may suggest that the cables are not yet ready to be installed. To mitigate such risks, the dielectric performance of newly installed 3C 500MMP XLPE cables was evaluated both before and after jointing and termination, prior to commissioning the new main substation. The assessment included Insulation Resistance (IR) and Dielectric Absorption Ratio (DAR) tests, along with continuity and a 24-hour soaking test to verify electrical connectivity and overall performance. The IR and DAR tests yielded results within acceptable ranges, with insulation resistance values exceeding 0.1 GΩ and DAR values above 1.6. Continuity tests confirmed proper jointing and termination, as evidenced by resistance values below 5 Ω. Furthermore, the absence of tripping incidents during the 24-hour soaking period provided additional assurance of the cables’ readiness for energization.

Journal of Power and Energy EngineeringVol. 13(09)
Universiti Teknikal Malaysia Melaka
Openalex Percentile: Top 81%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Dielectric Assessment of 11 kV Three-Core XLPE Power Cable during New Substation Commissioning — Mohd Amin Mohd Noh, Sharin Ab Ghani, et al. · Journal of Power and Energy Engineering (2025) | TGRS Research Map | TGRS