Provisions in international design standards for the axial capacity of slender concrete masonry wall (CMW) behaviour have been noted to be inaccurate. These inaccuracies may be conservative in some cases and unconservative in others. A limitation to the improvement of these provisions is the lack of CMW experimental data. Logistical issues associated with the size of full-scale specimens limits the experimental data available in the literature. Scaled specimens can reduce logistical constraints, but the behaviour of CMWs at scale is not well understood. To improve the understanding of scaled CMWs in the literature, 12 CMWs (6 full-scale, 6 half-scale) were built and tested in eccentric axial compression inducing symmetric single curvature, with e = t /3 for all specimens. Walls were tested 1 year after construction. Failure loads and lateral load-deflection profiles are provided for all specimens. The experimental data yield several key observations: increased variation in f’ m at half-scale (up to 9.9 %), and at 1 year compared to 28 days (up to 9.3 %); increased variability (3.2 %) in mortar joint thickness at half-scale; and similar behaviour at scale for all types of tested walls when accounting for expected variation in f’ m . A simplified test rig, eliminating the bottom roller typically used in slender CMW testing, was used in the test. The simplified test rig was found to induce no membrane action in all walls with h / t = 20 and is recommended for slender CMW testing due to its increased constructability. • 12 concrete masonry walls tested in eccentric axial compression at full, half scale. • Walls tested at 1 year of age; failure loads, load-deflection data provided. • Increased COV in grout, prism strengths noted at half scale and 1 year • No scale effects at half scale for masonry walls in eccentric axial compression. • Simplified test rig recommended for walls with h/t ≥ 20.

Authors

Institutions

Publication Details

Journal
Engineering Structures
Published
2025-09-08
DOI
https://doi.org/10.1016/j.engstruct.2025.121281
Primary Topic
Masonry and Concrete Structural Analysis
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An experimental study of eccentrically loaded slender concrete masonry walls at full- and half-scale

George Iskander, Nigel G. Shrive, Ali Ahmed
1 links
Engineering Structures
Masonry and Concrete Structural Analysis
article

An experimental study of eccentrically loaded slender concrete masonry walls at full- and half-scale

George Iskander, Nigel G. Shrive, Ali Ahmed
article en

Abstract

Provisions in international design standards for the axial capacity of slender concrete masonry wall (CMW) behaviour have been noted to be inaccurate. These inaccuracies may be conservative in some cases and unconservative in others. A limitation to the improvement of these provisions is the lack of CMW experimental data. Logistical issues associated with the size of full-scale specimens limits the experimental data available in the literature. Scaled specimens can reduce logistical constraints, but the behaviour of CMWs at scale is not well understood. To improve the understanding of scaled CMWs in the literature, 12 CMWs (6 full-scale, 6 half-scale) were built and tested in eccentric axial compression inducing symmetric single curvature, with e = t /3 for all specimens. Walls were tested 1 year after construction. Failure loads and lateral load-deflection profiles are provided for all specimens. The experimental data yield several key observations: increased variation in f’ m at half-scale (up to 9.9 %), and at 1 year compared to 28 days (up to 9.3 %); increased variability (3.2 %) in mortar joint thickness at half-scale; and similar behaviour at scale for all types of tested walls when accounting for expected variation in f’ m . A simplified test rig, eliminating the bottom roller typically used in slender CMW testing, was used in the test. The simplified test rig was found to induce no membrane action in all walls with h / t = 20 and is recommended for slender CMW testing due to its increased constructability. • 12 concrete masonry walls tested in eccentric axial compression at full, half scale. • Walls tested at 1 year of age; failure loads, load-deflection data provided. • Increased COV in grout, prism strengths noted at half scale and 1 year • No scale effects at half scale for masonry walls in eccentric axial compression. • Simplified test rig recommended for walls with h/t ≥ 20.

Engineering StructuresVol. 343
University of Calgary (CA)
Openalex Percentile: Top 74%
Masonry and Concrete Structural Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.