Identification of the Series Arc Fault Based on EMD Algorithm

An improved control theory arc model is proposed to control micro arc distance between two electric poles. An arc voltage wave is measured on an arc generation device to simulate serial arc fault in 220Vac-50Hz low-voltage distribution network. Arc identification based on empirical mode decomposition (EMD) algorithm is achieved to analyze the intrinsic mode functions (IMFs) under normal and fault condition. EMD decomposition under normal arcs and fault arcs is achieved to obtain a series of intrinsic mode components, which is beneficial to finish the identification of fault arcs. The maximum value of the IMF9 mode obtained by EMD decomposition can be used as one of the characteristic quantities for identifying fault arcs.

Authors

Institutions

Publication Details

Published
2025-08-03
DOI
https://doi.org/10.1109/iciea65512.2025.11148815
Citations
1
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.73
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Identification of the Series Arc Fault Based on EMD Algorithm

Yifeng Cheng, Binbin Zhang, Jiaqing Zhang
1 citations
Electrical Fault Detection and Protection
0.73
article

Identification of the Series Arc Fault Based on EMD Algorithm

Yifeng Cheng, Binbin Zhang, Jiaqing Zhang
article en
1 citations

Abstract

An improved control theory arc model is proposed to control micro arc distance between two electric poles. An arc voltage wave is measured on an arc generation device to simulate serial arc fault in 220Vac-50Hz low-voltage distribution network. Arc identification based on empirical mode decomposition (EMD) algorithm is achieved to analyze the intrinsic mode functions (IMFs) under normal and fault condition. EMD decomposition under normal arcs and fault arcs is achieved to obtain a series of intrinsic mode components, which is beneficial to finish the identification of fault arcs. The maximum value of the IMF9 mode obtained by EMD decomposition can be used as one of the characteristic quantities for identifying fault arcs.

State Grid Corporation of China (China) (CN)
Openalex Percentile: Top 24%
Electrical Fault Detection and Protection
0.73
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.