An Improved LightGBM-Based Method for Series Arc Fault Detection
As low-voltage distribution networks incorporate increasingly diverse loads, series arc faults exhibit weak characteristics that are easily masked by load currents, leading to high misjudgment rates in traditional detection methods. This paper proposes a series arc fault detection method based on an improved Light Gradient Boosting Machine (LightGBM) model. First, a test platform containing 12 household loads was built to collect arc data from both individual and composite loads. Composite loads refer to composite load conditions where multiple devices are running simultaneously and arcing occurs on some loads. To address the challenge of feature extraction, Variational Mode Decomposition (VMD) is employed to isolate the fundamental frequency component. To enhance high-frequency arc characteristics, singular value decomposition (SVD) is then applied. A multidimensional statistical feature set—comprising peak-to-peak value, kurtosis, and other indicators—is constructed. Finally, the LightGBM algorithm is used to identify arc faults based on these features. To overcome the LightGBM model’s limited ability to focus on hard-to-classify samples, a dynamic weighted hybrid loss function is developed. Experiments demonstrate that the proposed method achieves 98.9% accuracy across 223,615 sample groups. When deployed on STM32H723VGT6 hardware, the average fault alarm time is 83.8 ms, meeting requirements.
Authors
- Penghe Zhang (ORCID: https://orcid.org/0000-0001-6345-8332)
- Runan Song (ORCID: https://orcid.org/0000-0001-9042-5704)
- Yang Xue (ORCID: https://orcid.org/0000-0002-2018-1334)
- Jiaying Wang (ORCID: https://orcid.org/0000-0002-7907-9721)
- Zhongqiang Wu
Institutions
- North China Electric Power University (CN)
- China Electric Power Research Institute
Publication Details
- Journal
- Electronics
- Published
- 2025-09-10
- DOI
- https://doi.org/10.3390/electronics14183593
- Primary Topic
- Electrical Fault Detection and Protection
- Type
- article
- Field-Weighted Citation Impact
- 0.00