Research on Distance Protection Scheme for Single-Phase to Ground Faults in Active Distribution Networks with Gap-Grounded Transformers

When a single-phase to ground fault (SPGF) occurs near the main power source in an active distribution network, distance protection section II (DPS-II) located at the distributed generator (DG) side operates with a delay. In gap-grounded transformers, this delay can lead to gap breakdown due to neutral-point overvoltage, which adversely affects the operation of DPS-II on the DG side. To address this issue, this paper proposes an improved DPS designed for active distribution networks with gap-grounded transformers. First, the factors influencing the additional impedance are analyzed after gap breakdown. To mitigate the effects of the additional impedance on DPS performance, an improved DPS based on real short-circuit impedances is introduced for active distribution networks. This scheme utilizes the negative-sequence current distribution factor on the DG side to accurately calculate the additional impedance angle, ensuring reliable protection. Simulation results demonstrate that the proposed scheme effectively operates under forward faults across various DG capacities, fault locations, local loads, and fault transition resistances. In addition, it avoids tripping under reverse faults, thereby confirming its reliability and superiority.

Authors

Institutions

Publication Details

Journal
Protection and Control of Modern Power Systems
Published
2025-09-01
DOI
https://doi.org/10.23919/pcmp.2024.000287
Citations
1
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
1.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on Distance Protection Scheme for Single-Phase to Ground Faults in Active Distribution Networks with Gap-Grounded Transformers

Wanqi Yuan, Shaofan Zhang, Jing Wan, Huili Tian et al.
1 citations
Protection and Control of Modern Power Systems
Power Systems Fault Detection
1.21
article

Research on Distance Protection Scheme for Single-Phase to Ground Faults in Active Distribution Networks with Gap-Grounded Transformers

Wanqi Yuan, Shaofan Zhang, Jing Wan, Huili Tian, Xiaolong Chen, Yongli Li
article en
1 citations

Abstract

When a single-phase to ground fault (SPGF) occurs near the main power source in an active distribution network, distance protection section II (DPS-II) located at the distributed generator (DG) side operates with a delay. In gap-grounded transformers, this delay can lead to gap breakdown due to neutral-point overvoltage, which adversely affects the operation of DPS-II on the DG side. To address this issue, this paper proposes an improved DPS designed for active distribution networks with gap-grounded transformers. First, the factors influencing the additional impedance are analyzed after gap breakdown. To mitigate the effects of the additional impedance on DPS performance, an improved DPS based on real short-circuit impedances is introduced for active distribution networks. This scheme utilizes the negative-sequence current distribution factor on the DG side to accurately calculate the additional impedance angle, ensuring reliable protection. Simulation results demonstrate that the proposed scheme effectively operates under forward faults across various DG capacities, fault locations, local loads, and fault transition resistances. In addition, it avoids tripping under reverse faults, thereby confirming its reliability and superiority.

Protection and Control of Modern Power SystemsVol. 10(5)
Tianjin University (CN), Guangzhou Education Bureau (CN), China Southern Power Grid (China) (CN), Power Grid Corporation (India) (IN)
Openalex Percentile: Top 17%
Power Systems Fault Detection
1.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Research on Distance Protection Scheme for Single-Phase to Ground Faults in Active Distribution Networks with Gap-Grounded Transformers — Wanqi Yuan, Shaofan Zhang, et al. · Protection and Control of Modern Power Systems (2025) | TGRS Research Map | TGRS