Current Distortion Mitigation in Grid-Connected Three Phase NPC Converter in Presence of Grid Harmonic Voltage Pollution

The present paper reports the design of a grid-connected three-phase neutral point clamped (NPC) converter. Specifically, the voltage balancing, the LCL filter and the control system have been modelled and experimentally validated. Finally, the effect of the grid voltage harmonics on the NPC output currents was investigated, taking into account the voltage distortion defined according to the quality standard. The mitigation of the current distortions induced by the fifth and the seventh voltage harmonics was carried out using a notch filter compensator that has been specifically designed for this purpose. The mitigation of the proposed harmonic compensator under different operating conditions characterised by the presence of these voltage harmonics has been evaluated by means of an experimental test bench.

Authors

Institutions

Publication Details

Published
2025-06-24
DOI
https://doi.org/10.1109/iccep65222.2025.11143692
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Current Distortion Mitigation in Grid-Connected Three Phase NPC Converter in Presence of Grid Harmonic Voltage Pollution

Alfonso Damiano, Mauro Boi, Giuseppe Bossi
HVDC Systems and Fault Protection
article

Current Distortion Mitigation in Grid-Connected Three Phase NPC Converter in Presence of Grid Harmonic Voltage Pollution

Alfonso Damiano, Mauro Boi, Giuseppe Bossi
article en

Abstract

The present paper reports the design of a grid-connected three-phase neutral point clamped (NPC) converter. Specifically, the voltage balancing, the LCL filter and the control system have been modelled and experimentally validated. Finally, the effect of the grid voltage harmonics on the NPC output currents was investigated, taking into account the voltage distortion defined according to the quality standard. The mitigation of the current distortions induced by the fifth and the seventh voltage harmonics was carried out using a notch filter compensator that has been specifically designed for this purpose. The mitigation of the proposed harmonic compensator under different operating conditions characterised by the presence of these voltage harmonics has been evaluated by means of an experimental test bench.

University of Cagliari (IT)
Openalex Percentile: Top 77%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.