Evaluation of Temperature Distribution of Oil‐Immersed Transformer Considering Core Gap Insulation Using 3D Thermo‐Fluid Analysis During No‐Load Operation and Cooler Stoppage

ABSTRACT Previously, in temperature distribution analysis inside a transformer, there was an overall analysis that simulated the core and tank. However, insulators are not taken into consideration because the analysis cost increases. Therefore, the actual oil flow differs from the analysis results, and there is a possibility that the temperature may be evaluated higher than the actual oil flow, or the location of the hot spot may differ. In this study, we first focused on the temperature change around the core and took into the insulator, which greatly contributes to the oil flow. Next, the insulation in the gap between the cores is represented by thermal resistance. This has made it possible to analyze changes in oil flow and temperature distribution inside a transformer, taking insulators into account.

Authors

Institutions

Publication Details

Journal
Electrical Engineering in Japan
Published
2025-09-01
DOI
https://doi.org/10.1002/eej.23517
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of Temperature Distribution of Oil‐Immersed Transformer Considering Core Gap Insulation Using 3D Thermo‐Fluid Analysis During No‐Load Operation and Cooler Stoppage

Hiroaki Kojima, Kohei Yamaguchi, Naoyuki Kurita, Shinya Sugiyama et al.
4 links
Electrical Engineering in Japan
Power Transformer Diagnostics and Insulation
article

Evaluation of Temperature Distribution of Oil‐Immersed Transformer Considering Core Gap Insulation Using 3D Thermo‐Fluid Analysis During No‐Load Operation and Cooler Stoppage

Hiroaki Kojima, Kohei Yamaguchi, Naoyuki Kurita, Shinya Sugiyama, Kenichi Kawamura, Chie Kobayashi
article en

Abstract

ABSTRACT Previously, in temperature distribution analysis inside a transformer, there was an overall analysis that simulated the core and tank. However, insulators are not taken into consideration because the analysis cost increases. Therefore, the actual oil flow differs from the analysis results, and there is a possibility that the temperature may be evaluated higher than the actual oil flow, or the location of the hot spot may differ. In this study, we first focused on the temperature change around the core and took into the insulator, which greatly contributes to the oil flow. Next, the insulation in the gap between the cores is represented by thermal resistance. This has made it possible to analyze changes in oil flow and temperature distribution inside a transformer, taking insulators into account.

Electrical Engineering in JapanVol. 218(3)
Hitachi (Japan) (JP)
Openalex Percentile: Top 78%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Evaluation of Temperature Distribution of Oil‐Immersed Transformer Considering Core Gap Insulation Using 3D Thermo‐Fluid Analysis During No‐Load Operation and Cooler Stoppage — Hiroaki Kojima, Kohei Yamaguchi, et al. · Electrical Engineering in Japan (2025) | TGRS Research Map | TGRS