THE UTILIZATION OF ROOM AND BUILDING COMFORT EQUATION FOR REPORTING THERMAL COMFORT: A CASE STUDY AT LABORATORY BUILDINGS

As a tropical country, the government of Indonesia issued energy conservation standards for air conditioning systems in buildings through the Indonesian National Standard (SNI) 6390:2020. However, this SNI has not provided specific calculations to identify the comfort level of parameters in a building. This study aims to provide clear limits by providing conditions for fulfilling comfort conditions for indoor temperature parameters and buildings using a new proposed equation, namely the Room Comfort Equation (RCE) and Building Comfort Equation (BCE). These methods are based on the average ratio of room data parameters to SNI limited by a widening factor of 1% to 5% as comfort temperature tolerance threshold values. RCE is an Indoor temperature measurement compared to the SNI, resulting in a temperature parameter ratio . At the same time, BCE is the sum of the RCE across the building. The room temperature was measured for 4 weeks manually using a digital Environmental meter in four rooms , , and at the Integrated Laboratory and Technology Innovation Center (LTSIT) Building, University of Lampung. The calculation results obtained a temperature parameter ratio (RCE) of 0.958, 1.012, 1.002, and 0.990, so a BCE of 3.96 was obtained. This result shows that the building temperature is ideal by a 5% widening factor, but there are two rooms ( and ) has a passing tolerance limit of 1% widening factor. This finding successfully identified that the cause was the behavioural factor of busy users during practical hours. These results also show that room temperature comfort is more straightforward to measure and report. Therefore, additional efforts are needed to obtain the ideal/optimal temperature, such as upgrading HVAC systems with distributed adaptive control, which can be an effective temperature control solution while compensating for disturbances due to occupant behaviour and the influence of differing ambient weather conditions.

Authors

Institutions

Publication Details

Journal
ASEAN Engineering Journal
Published
2025-08-31
DOI
https://doi.org/10.11113/aej.v15.23449
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

THE UTILIZATION OF ROOM AND BUILDING COMFORT EQUATION FOR REPORTING THERMAL COMFORT: A CASE STUDY AT LABORATORY BUILDINGS

Tugiyono Tugiyono, Ahmad Zamil Zakaria, Suharno Suharno, Ahmad Dzakwan et al.
ASEAN Engineering Journal
Building Energy and Comfort Optimization
article

THE UTILIZATION OF ROOM AND BUILDING COMFORT EQUATION FOR REPORTING THERMAL COMFORT: A CASE STUDY AT LABORATORY BUILDINGS

Tugiyono Tugiyono, Ahmad Zamil Zakaria, Suharno Suharno, Ahmad Dzakwan, Sugiyanto Sugiyanto, Bayu Anggileo Pramesona
article en

Abstract

As a tropical country, the government of Indonesia issued energy conservation standards for air conditioning systems in buildings through the Indonesian National Standard (SNI) 6390:2020. However, this SNI has not provided specific calculations to identify the comfort level of parameters in a building. This study aims to provide clear limits by providing conditions for fulfilling comfort conditions for indoor temperature parameters and buildings using a new proposed equation, namely the Room Comfort Equation (RCE) and Building Comfort Equation (BCE). These methods are based on the average ratio of room data parameters to SNI limited by a widening factor of 1% to 5% as comfort temperature tolerance threshold values. RCE is an Indoor temperature measurement compared to the SNI, resulting in a temperature parameter ratio . At the same time, BCE is the sum of the RCE across the building. The room temperature was measured for 4 weeks manually using a digital Environmental meter in four rooms , , and at the Integrated Laboratory and Technology Innovation Center (LTSIT) Building, University of Lampung. The calculation results obtained a temperature parameter ratio (RCE) of 0.958, 1.012, 1.002, and 0.990, so a BCE of 3.96 was obtained. This result shows that the building temperature is ideal by a 5% widening factor, but there are two rooms ( and ) has a passing tolerance limit of 1% widening factor. This finding successfully identified that the cause was the behavioural factor of busy users during practical hours. These results also show that room temperature comfort is more straightforward to measure and report. Therefore, additional efforts are needed to obtain the ideal/optimal temperature, such as upgrading HVAC systems with distributed adaptive control, which can be an effective temperature control solution while compensating for disturbances due to occupant behaviour and the influence of differing ambient weather conditions.

ASEAN Engineering JournalVol. 15(3)
Lampung University (ID)
Universitas Lampung
Openalex Percentile: Top 75%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.