Effect of cable sheath termination on transient overvoltages due to high-frequency cable-transformer resonance

High-frequency resonances in cable-transformer systems can result in excessive overvoltages, increasing the probability of insulation failure for critical components such as power transformers. These resonances occur due to the interaction between the cable and transformer and are influenced by the cable’s characteristics, including the length and wave propagation velocity. In addition, the terminating impedances of the cable’s core and sheath conductors affect the resonance characteristic of the cable as well. Applying single-point sheath grounding to the high-voltage cable connecting the switchgear to the power transformer is conventional. This paper demonstrates that the cable-transformer resonances and resulting overvoltages can vary significantly depending on the end at which the sheath conductors are grounded. An in-depth investigation of such effects is carried out through rigorous mathematical analysis, followed by experimental validation and simulations in an electromagnetic transient (EMT)-based software using models that properly represent the equipment behaviors in a wide-frequency range. The results indicate that sheath conductor grounding configuration can profoundly affect the system response, influencing the severity of transient overvoltages caused by cable-transformer resonances. • Analyzing cable-sheath termination effects on HF cable-transformer resonances. • Considering sheath grounding at both ends, grid-end only, and transformer-end only. • Resonances and OVs are suppressed with single-point grounding at transformer side. • Study validated by mathematical analysis, EMTP simulations, and lab experiments.

Authors

Institutions

Publication Details

Journal
Electric Power Systems Research
Published
2025-08-29
DOI
https://doi.org/10.1016/j.epsr.2025.112130
Citations
1
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
1.15
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effect of cable sheath termination on transient overvoltages due to high-frequency cable-transformer resonance

Mohamad Ghaffarian Niasar, Marjan Popov, Behzad Behdani
1 citations
Electric Power Systems Research
Lightning and Electromagnetic Phenomena
1.15
article

Effect of cable sheath termination on transient overvoltages due to high-frequency cable-transformer resonance

Mohamad Ghaffarian Niasar, Marjan Popov, Behzad Behdani
article en
1 citations

Abstract

High-frequency resonances in cable-transformer systems can result in excessive overvoltages, increasing the probability of insulation failure for critical components such as power transformers. These resonances occur due to the interaction between the cable and transformer and are influenced by the cable’s characteristics, including the length and wave propagation velocity. In addition, the terminating impedances of the cable’s core and sheath conductors affect the resonance characteristic of the cable as well. Applying single-point sheath grounding to the high-voltage cable connecting the switchgear to the power transformer is conventional. This paper demonstrates that the cable-transformer resonances and resulting overvoltages can vary significantly depending on the end at which the sheath conductors are grounded. An in-depth investigation of such effects is carried out through rigorous mathematical analysis, followed by experimental validation and simulations in an electromagnetic transient (EMT)-based software using models that properly represent the equipment behaviors in a wide-frequency range. The results indicate that sheath conductor grounding configuration can profoundly affect the system response, influencing the severity of transient overvoltages caused by cable-transformer resonances. • Analyzing cable-sheath termination effects on HF cable-transformer resonances. • Considering sheath grounding at both ends, grid-end only, and transformer-end only. • Resonances and OVs are suppressed with single-point grounding at transformer side. • Study validated by mathematical analysis, EMTP simulations, and lab experiments.

Electric Power Systems ResearchVol. 250
Delft University of Technology (NL)
Affordable and clean energy
Openalex Percentile: Top 17%
Lightning and Electromagnetic Phenomena
1.15
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Effect of cable sheath termination on transient overvoltages due to high-frequency cable-transformer resonance — Mohamad Ghaffarian Niasar, Marjan Popov, et al. · Electric Power Systems Research (2025) | TGRS Research Map | TGRS