Surface Charge Accumulation of Cylindrical Insulator in Atmospheric Pressure Air After Positive and Negative Impulse Flashover

Atmospheric or compressed air exhibits adequate insulating properties for electrical insulation applications, making it a eco-friendly alternative to global warming <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{SF}_{6}$</tex> gas. However, surface insulation remains the weakest link in air-insulated electrical equipment, especially when the insulator endures transient impulse voltages and undertakes residual surface charges caused by impulse flashover. Investigating the charge characteristics at gas-solid interfaces and the evolution of discharges in air is crucial for improving the design of environmentally friendly, high voltage electrical apparatus. In this study, a cylindrical insulator was designed to study the surface charge accumulation after positive or negative lightening impulses. A charge measurement platform for gas-polymer surface discharge was constructed to measure charge density distribution. The results indicate under positive impulse voltage, the boundary between leader and streamer discharges is located approximately 20 mm from the high-voltage electrode. Under negative impulse voltage, this boundary gradually moves toward the ground electrode as the voltage increases. In the impulse voltage range of 12.5 kV to 16 kV, the separation threshold of charge density between leader and streamer discharges is between 350 and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$680 \text{pC} / \text{mm}^{2}$</tex>, with the transverse potential boundary around 9 kV and the longitudinal potential boundary between 6 kV and 8 kV. In the negative impulse voltage range of −9.5 kV to 17.5 kV, the threshold of charge density is between 500 and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$600 \text{pC} / \text{mm}^{2}$</tex>, the average field strength in the streamer region is between <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$1.0 \text{kV} / \text{mm}$</tex> and 1.6 <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{kV} / \text{mm}$</tex>, and the field strength in the leader channel is between <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$0.15 \text{kV} / \text{mm}$</tex> and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$0.20 \text{kV} / \text{mm}$</tex>. This study can provide some references to the development of high voltage, air insulated power switchgears, especially for applications under DC voltage.

Authors

Institutions

Publication Details

Published
2025-08-03
DOI
https://doi.org/10.1109/icempe66159.2025.11122917
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Surface Charge Accumulation of Cylindrical Insulator in Atmospheric Pressure Air After Positive and Negative Impulse Flashover

Kai Ma, Xinwei Li, Jinyu Wang, Guan Chen et al.
High voltage insulation and dielectric phenomena
article

Surface Charge Accumulation of Cylindrical Insulator in Atmospheric Pressure Air After Positive and Negative Impulse Flashover

Kai Ma, Xinwei Li, Jinyu Wang, Guan Chen, Han Jiang, Xiaoguang Zheng
article en

Abstract

Atmospheric or compressed air exhibits adequate insulating properties for electrical insulation applications, making it a eco-friendly alternative to global warming <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{SF}_{6}$</tex> gas. However, surface insulation remains the weakest link in air-insulated electrical equipment, especially when the insulator endures transient impulse voltages and undertakes residual surface charges caused by impulse flashover. Investigating the charge characteristics at gas-solid interfaces and the evolution of discharges in air is crucial for improving the design of environmentally friendly, high voltage electrical apparatus. In this study, a cylindrical insulator was designed to study the surface charge accumulation after positive or negative lightening impulses. A charge measurement platform for gas-polymer surface discharge was constructed to measure charge density distribution. The results indicate under positive impulse voltage, the boundary between leader and streamer discharges is located approximately 20 mm from the high-voltage electrode. Under negative impulse voltage, this boundary gradually moves toward the ground electrode as the voltage increases. In the impulse voltage range of 12.5 kV to 16 kV, the separation threshold of charge density between leader and streamer discharges is between 350 and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$680 \text{pC} / \text{mm}^{2}$</tex>, with the transverse potential boundary around 9 kV and the longitudinal potential boundary between 6 kV and 8 kV. In the negative impulse voltage range of −9.5 kV to 17.5 kV, the threshold of charge density is between 500 and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$600 \text{pC} / \text{mm}^{2}$</tex>, the average field strength in the streamer region is between <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$1.0 \text{kV} / \text{mm}$</tex> and 1.6 <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\text{kV} / \text{mm}$</tex>, and the field strength in the leader channel is between <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$0.15 \text{kV} / \text{mm}$</tex> and <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$0.20 \text{kV} / \text{mm}$</tex>. This study can provide some references to the development of high voltage, air insulated power switchgears, especially for applications under DC voltage.

China XD Group (China) (CN), China Southern Power Grid (China) (CN), Power Grid Corporation (India) (IN)
Openalex Percentile: Top 84%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.