Effect of Temperature on Partial Discharge Feature in a Void in Polypropylene Blends as Cable Insulation
Power cable is an essential component of power system, its reliability is critical for grid stability. Polypropylene (PP)/elastomer blends have great potential to be used as AC cable insulation. However, voids tend to appear in the blends due to long-term operation with thermal cycle, which would trigger partial discharge (PD) that degrades the insulation. In this paper, the temperature-dependent <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$P D$</tex> features in an artificial void within PP and PP/propylene-based elastomer (PBE) blend have been investigated. The PD signals are measured by a high frequency current transformer (HFCT) at temperatures of <tex xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">$\mathbf{2 5 - 8 5}{ }^{\boldsymbol{\circ}} \mathrm{C}$</tex>, the phase resolved partial discharge (PRPD) pattern are employed to estimate the influence of temperature on the PD activity. The test results indicated that the iPP/PBE blend exhibited higher discharge peaks at elevated temperatures, while pure iPP showed more stable discharge rate with temperature.
Authors
- Di Lu (ORCID: https://orcid.org/0000-0001-9860-3173)
- Yu Gao (ORCID: https://orcid.org/0000-0002-0493-8421)
- Risheng Pei (ORCID: https://orcid.org/0000-0001-8595-2702)
- Qi Shang (ORCID: https://orcid.org/0000-0001-9135-2666)
- Tao Han (ORCID: https://orcid.org/0000-0003-3602-4859)
- Zhilong Yu
- Boxue X. Du (ORCID: https://orcid.org/0000-0002-7500-1134)
- Bosen Si (ORCID: https://orcid.org/0009-0003-3142-9811)
Institutions
- Tianjin University (CN)
Publication Details
- Published
- 2025-08-03
- DOI
- https://doi.org/10.1109/icempe66159.2025.11123114
- Primary Topic
- High voltage insulation and dielectric phenomena
- Type
- article
- Field-Weighted Citation Impact
- 0.00