Comprehensive Research and Measurement on the Influencing Factors of Grounding Current of Converter Transformer Core and Clamp System

The influencing factors and generation mechanism of grounding current of converter transformer core and clamp system are still unclear. It is difficult for on-site operation and maintenance personnel to make timely and accurate judgments when they encounter related problems. In this article, the influencing mechanism behind grounding current generation in the converter transformer core and clamp is analyzed through theoretical analysis, equivalent parameter calculations, experimental measurements, finite-element method (FEM), digital simulations, and experimental verification. Factors such as grounding path, core type, connection type, voltage harmonics, coil arrangement and insulation parameter are considered. To simplify the calculation, a method for calculating the equivalent relative permittivity of insulation materials is proposed, supported by experimental measurements. Additionally, parasitic capacitance between components is calculated based on FEM. A model of the grounding current system is established to calculate and analyze the grounding current. The findings reveal that harmonic voltage from converter valve operations is the primary cause of elevated grounding currents. Excluding harmonic factors, the influence of temperature on the dielectric parameters of insulating materials is the second main factor in the change of grounding current. When the converter transformer is heated from 0 ° to 80 °, the grounding current will increase by 41.11% . Finally, on-site measurements of grounding current from a 412.3 MVA converter transformer are compared with calculated results to validate the proposed study, providing a theoretical basis for establish future standard. And according to the results of this article, the operation and maintenance personnel will not misjudge the grounding current due to excessive voltage harmonics or temperature fluctuations, and avoid to carry out power outage maintenance, affecting the power system.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Electronics
Published
2025-08-14
DOI
https://doi.org/10.1109/tpel.2025.3599167
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Comprehensive Research and Measurement on the Influencing Factors of Grounding Current of Converter Transformer Core and Clamp System

Xiu Zhou, Haonan Bai, Xiaofeng Zheng, Guoxin Zhao et al.
IEEE Transactions on Power Electronics
High-Voltage Power Transmission Systems
article

Comprehensive Research and Measurement on the Influencing Factors of Grounding Current of Converter Transformer Core and Clamp System

Xiu Zhou, Haonan Bai, Xiaofeng Zheng, Guoxin Zhao, Dezhi Chen, Zhongxiang Xin
article en

Abstract

The influencing factors and generation mechanism of grounding current of converter transformer core and clamp system are still unclear. It is difficult for on-site operation and maintenance personnel to make timely and accurate judgments when they encounter related problems. In this article, the influencing mechanism behind grounding current generation in the converter transformer core and clamp is analyzed through theoretical analysis, equivalent parameter calculations, experimental measurements, finite-element method (FEM), digital simulations, and experimental verification. Factors such as grounding path, core type, connection type, voltage harmonics, coil arrangement and insulation parameter are considered. To simplify the calculation, a method for calculating the equivalent relative permittivity of insulation materials is proposed, supported by experimental measurements. Additionally, parasitic capacitance between components is calculated based on FEM. A model of the grounding current system is established to calculate and analyze the grounding current. The findings reveal that harmonic voltage from converter valve operations is the primary cause of elevated grounding currents. Excluding harmonic factors, the influence of temperature on the dielectric parameters of insulating materials is the second main factor in the change of grounding current. When the converter transformer is heated from 0 ° to 80 °, the grounding current will increase by 41.11% . Finally, on-site measurements of grounding current from a 412.3 MVA converter transformer are compared with calculated results to validate the proposed study, providing a theoretical basis for establish future standard. And according to the results of this article, the operation and maintenance personnel will not misjudge the grounding current due to excessive voltage harmonics or temperature fluctuations, and avoid to carry out power outage maintenance, affecting the power system.

IEEE Transactions on Power ElectronicsVol. 41(2)
Electric Power Research Institute (US), Shenyang University of Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 79%
High-Voltage Power Transmission Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.