On-Line Partial Discharge Diagnosis on Stator Winding Insulation: Impacts of Voltage Distortion and Winding Temperature

Partial discharge (PD) magnitude and phase-resolved PD (PRPD) patterns are key indicators for on-line PD diagnosis for stator windings. These indicators can be influenced by generator operating conditions because generators are subjected to high temperatures and voltage distortion. This study investigates the impacts of voltage distortion and winding temperature on on-line PD diagnosis. We measure PDs in stator windings of a hydrogenerator. The voltage waveform and winding temperature varied with the load condition. Harmonic voltages of about 2–4 kHz are superimposed on the generator voltage. The temperature ranges from 27°C to 70°C. Although the superimposition of the harmonic voltages altered the PRPD pattern, its effect on PD magnitude remains negligible. In contrast, the shape of the PRPD pattern is independent of the temperature, whereas the PD magnitude decreases with the temperature. Based on these findings, we state notes for conducting on-line PD diagnosis under varying generator conditions.

Authors

Institutions

Publication Details

Published
2025-06-08
DOI
https://doi.org/10.1109/eic63069.2025.11123288
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

On-Line Partial Discharge Diagnosis on Stator Winding Insulation: Impacts of Voltage Distortion and Winding Temperature

Satoru Miyazaki, Shin Nakamura, Takashi Kuraishi
High voltage insulation and dielectric phenomena
article

On-Line Partial Discharge Diagnosis on Stator Winding Insulation: Impacts of Voltage Distortion and Winding Temperature

Satoru Miyazaki, Shin Nakamura, Takashi Kuraishi
article en

Abstract

Partial discharge (PD) magnitude and phase-resolved PD (PRPD) patterns are key indicators for on-line PD diagnosis for stator windings. These indicators can be influenced by generator operating conditions because generators are subjected to high temperatures and voltage distortion. This study investigates the impacts of voltage distortion and winding temperature on on-line PD diagnosis. We measure PDs in stator windings of a hydrogenerator. The voltage waveform and winding temperature varied with the load condition. Harmonic voltages of about 2–4 kHz are superimposed on the generator voltage. The temperature ranges from 27°C to 70°C. Although the superimposition of the harmonic voltages altered the PRPD pattern, its effect on PD magnitude remains negligible. In contrast, the shape of the PRPD pattern is independent of the temperature, whereas the PD magnitude decreases with the temperature. Based on these findings, we state notes for conducting on-line PD diagnosis under varying generator conditions.

Central Research Institute of Electric Power Industry (JP)
Affordable and clean energy
Openalex Percentile: Top 84%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.