Assessing the insulation condition of high-voltage equipment using non-intrusive partial discharge (PD) measurement is widespread nowadays. The transient earth voltage (TEV) method, a relatively new non-intrusive approach, operates by detecting the surface current induced by electromagnetic waves (EM) propagating from PD, which spreads out through the discontinuities of the equipment's outer surface. This paper evaluates the performance of TEV sensors compared to the IEC 60270 standard for detecting PD caused by various defect types inside and outside a metal enclosure in a laboratory setting. Phaseresolved PD (PRPD) pattern and fast Fourier transform (FFT) indicate that each defect has its own characteristic. The FFT analysis reveals that PD can only be effectively detected at specific frequencies where it is distinguishable from background noise.

Authors

Institutions

Publication Details

Published
2025-06-08
DOI
https://doi.org/10.1109/eic63069.2025.11123381
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

TEV Sensor-Based PD Measurements with a Focus on PRPD Patterns and FFT Analysis

Éric David, Mathieu Lachance, Mahdi Abbasi
High voltage insulation and dielectric phenomena
article

TEV Sensor-Based PD Measurements with a Focus on PRPD Patterns and FFT Analysis

Éric David, Mathieu Lachance, Mahdi Abbasi
article en

Abstract

Assessing the insulation condition of high-voltage equipment using non-intrusive partial discharge (PD) measurement is widespread nowadays. The transient earth voltage (TEV) method, a relatively new non-intrusive approach, operates by detecting the surface current induced by electromagnetic waves (EM) propagating from PD, which spreads out through the discontinuities of the equipment's outer surface. This paper evaluates the performance of TEV sensors compared to the IEC 60270 standard for detecting PD caused by various defect types inside and outside a metal enclosure in a laboratory setting. Phaseresolved PD (PRPD) pattern and fast Fourier transform (FFT) indicate that each defect has its own characteristic. The FFT analysis reveals that PD can only be effectively detected at specific frequencies where it is distinguishable from background noise.

Omron (Japan) (JP), Xenobe Research Institute (US)
Openalex Percentile: Top 84%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

TEV Sensor-Based PD Measurements with a Focus on PRPD Patterns and FFT Analysis — Éric David, Mathieu Lachance, et al. · (2025) | TGRS Research Map | TGRS