Analysis of the Sensitivity of the No-Load Current Measuring to Detect Short Circuits Between Transformer Winding Turns

Short circuits between winding turns are one of the most common and potentially destructive electrical faults in transformers. This paper analyzes the sensitivity of magnitude changes of the harmonic components in the transformer no-load current to detect turn-to-turn faults. Simulations were used to evaluate the technical feasibility of the proposed test in a singlephase high-power transformer and a three-phase low power transformer. Additionally, in the case of the three-phase transformer, measurements were made experimentally, applying turn-to-turn faults in the winding of one of the phases and analyzing their harmonic content. Finally, it is shown how the reduction in the ratio between the third harmonic and the fundamental component magnitudes is a viable indicator to detect incipient insulation faults between turns.

Authors

Institutions

Publication Details

Published
2025-06-08
DOI
https://doi.org/10.1109/eic63069.2025.11123240
Primary Topic
Non-Destructive Testing Techniques
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of the Sensitivity of the No-Load Current Measuring to Detect Short Circuits Between Transformer Winding Turns

Rodrigo Ocón-Valdez, Fermín P. Espino‐Cortés, C. Paulina Bravo-Ortega
Non-Destructive Testing Techniques
article

Analysis of the Sensitivity of the No-Load Current Measuring to Detect Short Circuits Between Transformer Winding Turns

Rodrigo Ocón-Valdez, Fermín P. Espino‐Cortés, C. Paulina Bravo-Ortega
article en

Abstract

Short circuits between winding turns are one of the most common and potentially destructive electrical faults in transformers. This paper analyzes the sensitivity of magnitude changes of the harmonic components in the transformer no-load current to detect turn-to-turn faults. Simulations were used to evaluate the technical feasibility of the proposed test in a singlephase high-power transformer and a three-phase low power transformer. Additionally, in the case of the three-phase transformer, measurements were made experimentally, applying turn-to-turn faults in the winding of one of the phases and analyzing their harmonic content. Finally, it is shown how the reduction in the ratio between the third harmonic and the fundamental component magnitudes is a viable indicator to detect incipient insulation faults between turns.

X-Fab (Germany) (DE), China XD Group (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 78%
Non-Destructive Testing Techniques
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.