A new approach to measuring angular-dependent transmittance values of extended complex fenestration systems with a near field goniophotometer

• A near field goniophotometer was realized using an angle filter at the detector. • Comparison of near field and far field goniophotometer revealed strong agreement. • Ray tracing simulation exhibited low absolute errors for direct-direct transmission. • The simulation replicated the scattering effect of a mirror lamella. The knowledge of angle-dependent transmittance values is crucial for many areas in the built environment, such as visual and thermal comfort assessment or energy demand calculation. Measurement devices used for complex fenestration systems are typically far field goniophotometers, which require a large distance between sample and detector. As alternative to conventional far field devices, a near field goniophotometer to measure angle-dependent transmittance values of shading systems was developed. The new device is aimed at extended shading systems with structural elements, such as blind systems. This is realized by combining large-area detectors with an angle filter of a specific angular sensitivity curve. The measurement principle and prototypical setup are explained and requirements of divergence of the light source and the detector are formulated followed by a thorough discussion of the results. A comparison between near field and far field measurements was carried out. A raytracing simulation model that replicates the measurement procedure was used for comparison with measured data. All measurements were carried out with an artificial light source and fixed incidence angles in normal direction to the sample. The comparison of measured and simulated transmittance showed low absolute errors. The scattering effect of a mirror lamella found in the measurement could be replicated by the simulation. Some differences in absolute transmittance of the mirror lamella, which might be caused by effects that are not covered in the simulation model, were found between measurement and simulation. A qualitative and quantitative analysis of errors and uncertainty was carried out.

Authors

Institutions

Publication Details

Journal
Measurement
Published
2025-08-22
DOI
https://doi.org/10.1016/j.measurement.2025.118751
Citations
1
Primary Topic
Calibration and Measurement Techniques
Type
article
Field-Weighted Citation Impact
4.99

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A new approach to measuring angular-dependent transmittance values of extended complex fenestration systems with a near field goniophotometer

Christian Hagendorf, Lars Oliver Grobe, Charlotte Pfau, Marko Turek et al.
1 citations
Measurement
Calibration and Measurement Techniques
4.99
article

A new approach to measuring angular-dependent transmittance values of extended complex fenestration systems with a near field goniophotometer

Christian Hagendorf, Lars Oliver Grobe, Charlotte Pfau, Marko Turek, David Geisler‐Moroder, Margarita Alwalidi, Sabine Hoffmann, Sarith Subramaniam, Saikumar Deshaboina
article en
1 citations

Abstract

• A near field goniophotometer was realized using an angle filter at the detector. • Comparison of near field and far field goniophotometer revealed strong agreement. • Ray tracing simulation exhibited low absolute errors for direct-direct transmission. • The simulation replicated the scattering effect of a mirror lamella. The knowledge of angle-dependent transmittance values is crucial for many areas in the built environment, such as visual and thermal comfort assessment or energy demand calculation. Measurement devices used for complex fenestration systems are typically far field goniophotometers, which require a large distance between sample and detector. As alternative to conventional far field devices, a near field goniophotometer to measure angle-dependent transmittance values of shading systems was developed. The new device is aimed at extended shading systems with structural elements, such as blind systems. This is realized by combining large-area detectors with an angle filter of a specific angular sensitivity curve. The measurement principle and prototypical setup are explained and requirements of divergence of the light source and the detector are formulated followed by a thorough discussion of the results. A comparison between near field and far field measurements was carried out. A raytracing simulation model that replicates the measurement procedure was used for comparison with measured data. All measurements were carried out with an artificial light source and fixed incidence angles in normal direction to the sample. The comparison of measured and simulated transmittance showed low absolute errors. The scattering effect of a mirror lamella found in the measurement could be replicated by the simulation. Some differences in absolute transmittance of the mirror lamella, which might be caused by effects that are not covered in the simulation model, were found between measurement and simulation. A qualitative and quantitative analysis of errors and uncertainty was carried out.

MeasurementVol. 257
University of Kaiserslautern (DE), Universität Innsbruck (AT), ETH Zurich (CH), Fraunhofer Institute for Microstructure of Materials and Systems (DE), Fraunhofer Center for Silicon Photovoltaics (DE), University of Applied Sciences Kaiserslautern (DE)
Bundesministerium für Wirtschaft und Energie
Openalex Percentile: Top 5%
Calibration and Measurement Techniques
4.99
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.