Electric Field-Dependent XY Equivalent Structure Modeling of Oil-Paper Insulation Systems in Power Transformers: Improvement and Verification

XY equivalent structure model plays a crucial role in characterizing insulation states of oil-paper insulation system (OPIS) in power transformers based on frequency domain spectroscopy (FDS). However, the conventional modeling method of OPIS only considers simplified calculation of complex permittivity for insulating mineral oil (IMO) under low field. This could cause large deviations and cannot meet high-field reality. Therefore, this paper develops a new XY equivalent structure model to characterize insulation dielectric performance of OPIS including IMO and oil-impregnated paperboard (OIP) based on high-field FDS. Firstly, the modeling processes of XY model of OPIS are investigated as a function of electric field. Then, the complex permittivity behaviors of IMO, OIP and OPIS subject to diverse electric fields are discussed, respectively. Subsequently, according to high-field dielectric behaviors, a new calculation approach of complex permittivity of IMO is proposed introducing two field-related parameters and an electric field enhancement factor τ(E). Finally, the effectiveness of new field-dependent XY model for OPIS is validated using high-field complex permittivity of IMO. Compared to traditional model, this work can accurately characterize field-dependent dielectric behaviors of OPIS in power transformers. This article will provide a solid foundation for health management and prognostics of OPIS in power transformers.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Dielectrics and Electrical Insulation
Published
2025-08-20
DOI
https://doi.org/10.1109/tdei.2025.3600558
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Electric Field-Dependent XY Equivalent Structure Modeling of Oil-Paper Insulation Systems in Power Transformers: Improvement and Verification

Shilin Shi, Qian Zeng, Guochao Qian, Weiju Dai et al.
IEEE Transactions on Dielectrics and Electrical Insulation
Power Transformer Diagnostics and Insulation
article

Electric Field-Dependent XY Equivalent Structure Modeling of Oil-Paper Insulation Systems in Power Transformers: Improvement and Verification

Shilin Shi, Qian Zeng, Guochao Qian, Weiju Dai, Jian Hao, Xize Dai
article en

Abstract

XY equivalent structure model plays a crucial role in characterizing insulation states of oil-paper insulation system (OPIS) in power transformers based on frequency domain spectroscopy (FDS). However, the conventional modeling method of OPIS only considers simplified calculation of complex permittivity for insulating mineral oil (IMO) under low field. This could cause large deviations and cannot meet high-field reality. Therefore, this paper develops a new XY equivalent structure model to characterize insulation dielectric performance of OPIS including IMO and oil-impregnated paperboard (OIP) based on high-field FDS. Firstly, the modeling processes of XY model of OPIS are investigated as a function of electric field. Then, the complex permittivity behaviors of IMO, OIP and OPIS subject to diverse electric fields are discussed, respectively. Subsequently, according to high-field dielectric behaviors, a new calculation approach of complex permittivity of IMO is proposed introducing two field-related parameters and an electric field enhancement factor τ(E). Finally, the effectiveness of new field-dependent XY model for OPIS is validated using high-field complex permittivity of IMO. Compared to traditional model, this work can accurately characterize field-dependent dielectric behaviors of OPIS in power transformers. This article will provide a solid foundation for health management and prognostics of OPIS in power transformers.

IEEE Transactions on Dielectrics and Electrical InsulationVol. 32(5)
Chongqing University (CN), China Southern Power Grid (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 80%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.