Use of fast circuit breakers to mitigate overvoltages in VSC HVDC point-to-point schemes

Sustained DC-side overvoltages in HVDC point-to-point schemes may occur on the healthy pole when DC-side pole-to-ground faults occur. Until now, the impact of these DC-side overvoltages on cable systems is not well known. Several mitigation methods have been proposed until now, including actively switched DC- or AC-side surge arresters. This paper investigates the potential of using fast AC-side or DC-side circuit breakers for mitigating DC-side overvoltages using EMT analysis. To reduce peak overvoltages, any AC- or DC-side circuit breaker solution must be sufficiently fast acting, even though all investigated solutions show limited potential. All investigated solutions show that sustained overvoltages can be mitigated, thereby reducing DC-side surge arrester requirements at a limited energy absorption requirements of the AC- or DC-side circuit breaker. The simulation-based study should be complemented with investigations towards the practical realization of such solutions. • In symmetrical monopolar schemes, overvoltages may appear during DC-side pole-to-ground faults. • Fast circuit breakers at AC or DC side can mitigate these DC-side overvoltages, especially with respect to the duration. • In all studied EMT cases, the burden on the pole arresters is heavily reduced at only a moderate breaker arrester energy.

Authors

Institutions

Publication Details

Journal
Electric Power Systems Research
Published
2025-08-18
DOI
https://doi.org/10.1016/j.epsr.2025.112050
Citations
1
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.73
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Use of fast circuit breakers to mitigate overvoltages in VSC HVDC point-to-point schemes

Willem Leterme, Mudar Abedrabbo
1 citations
Electric Power Systems Research
HVDC Systems and Fault Protection
0.73
article

Use of fast circuit breakers to mitigate overvoltages in VSC HVDC point-to-point schemes

Willem Leterme, Mudar Abedrabbo
article en
1 citations

Abstract

Sustained DC-side overvoltages in HVDC point-to-point schemes may occur on the healthy pole when DC-side pole-to-ground faults occur. Until now, the impact of these DC-side overvoltages on cable systems is not well known. Several mitigation methods have been proposed until now, including actively switched DC- or AC-side surge arresters. This paper investigates the potential of using fast AC-side or DC-side circuit breakers for mitigating DC-side overvoltages using EMT analysis. To reduce peak overvoltages, any AC- or DC-side circuit breaker solution must be sufficiently fast acting, even though all investigated solutions show limited potential. All investigated solutions show that sustained overvoltages can be mitigated, thereby reducing DC-side surge arrester requirements at a limited energy absorption requirements of the AC- or DC-side circuit breaker. The simulation-based study should be complemented with investigations towards the practical realization of such solutions. • In symmetrical monopolar schemes, overvoltages may appear during DC-side pole-to-ground faults. • Fast circuit breakers at AC or DC side can mitigate these DC-side overvoltages, especially with respect to the duration. • In all studied EMT cases, the burden on the pole arresters is heavily reduced at only a moderate breaker arrester energy.

Electric Power Systems ResearchVol. 250
National Grid (United States) (US), RWTH Aachen University (DE), KU Leuven (BE)
Affordable and clean energy
Openalex Percentile: Top 25%
HVDC Systems and Fault Protection
0.73
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Use of fast circuit breakers to mitigate overvoltages in VSC HVDC point-to-point schemes — Willem Leterme, Mudar Abedrabbo · Electric Power Systems Research (2025) | TGRS Research Map | TGRS