This study aimed to identify the optimal outdoor air (OA) intake temperature range for the application of a dry-bulb temperature-based air-side economizer in data centers. To this end, a series of parametric simulations was conducted using EnergyPlus (version 24.1.0) and a previously validated small-to-medium-scale data center model situated in Daejeon, South Korea (ASHRAE Climate Zone 4A). A parametric analysis was performed by varying the maximum allowable OA intake dry-bulb temperature from 10 to 18 °C in 2 °C increments. The simulation results indicated that OA intake was limited during the summer due to high humidity levels, whereas it was more viable during the winter and interseason period. However, when the maximum OA intake dry-bulb temperature exceeded 14 °C, the increase in latent heat load caused humidity increased overall energy consumption. To expand the applicable range for air-side economizer operation, the cooling system capacity was adjusted. The scenario with a 14 °C OA threshold demonstrated the most favorable balance between energy efficiency and compliance with operating environmental criteria. The findings of this study provide a technical basis for establishing OA intake guidelines in dry-bulb temperature-based economizer control. However, further field-based validation is required to verify the effectiveness of these simulation results under real-world operating conditions.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2025-08-17
DOI
https://doi.org/10.3390/buildings15162913
Primary Topic
Cloud Computing and Resource Management
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers

Dongsu Kim, Sung Lok, Suh-hyun Kwon, Minho Kim et al.
Buildings
Cloud Computing and Resource Management
article

Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers

Dongsu Kim, Sung Lok, Suh-hyun Kwon, Minho Kim, Ahmin Jang
article en

Abstract

This study aimed to identify the optimal outdoor air (OA) intake temperature range for the application of a dry-bulb temperature-based air-side economizer in data centers. To this end, a series of parametric simulations was conducted using EnergyPlus (version 24.1.0) and a previously validated small-to-medium-scale data center model situated in Daejeon, South Korea (ASHRAE Climate Zone 4A). A parametric analysis was performed by varying the maximum allowable OA intake dry-bulb temperature from 10 to 18 °C in 2 °C increments. The simulation results indicated that OA intake was limited during the summer due to high humidity levels, whereas it was more viable during the winter and interseason period. However, when the maximum OA intake dry-bulb temperature exceeded 14 °C, the increase in latent heat load caused humidity increased overall energy consumption. To expand the applicable range for air-side economizer operation, the cooling system capacity was adjusted. The scenario with a 14 °C OA threshold demonstrated the most favorable balance between energy efficiency and compliance with operating environmental criteria. The findings of this study provide a technical basis for establishing OA intake guidelines in dry-bulb temperature-based economizer control. However, further field-based validation is required to verify the effectiveness of these simulation results under real-world operating conditions.

BuildingsVol. 15(16)
Hanbat National University (KR), Mokwon University (KR)
National Research Foundation of Korea
Openalex Percentile: Top 69%
Cloud Computing and Resource Management
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.