Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50

• First pool boiling evaluation of 2P50 for two-phase immersion cooling • 2P50 shows up to 59% higher heat transfer coefficient (HTC) than HFE-7100 • 2P50’s CHF is comparable but 5.9%–9.9% lower than HFE-7100 under test conditions • Optimized Cooper correlation predicts HTC with 5.3% MAE for 2P50 The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m 2 ) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.

Authors

Institutions

Publication Details

Journal
International Journal of Thermofluids
Published
2025-08-18
DOI
https://doi.org/10.1016/j.ijft.2025.101379
Citations
2
Primary Topic
Heat Transfer and Boiling Studies
Type
article
Field-Weighted Citation Impact
1.43
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50

Yifeng Hu, M. Muneeshwaran, Samuel F. Yana Motta, Cheng-Min Yang et al.
2 citations
International Journal of Thermofluids
Heat Transfer and Boiling Studies
1.43
article

Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50

Yifeng Hu, M. Muneeshwaran, Samuel F. Yana Motta, Cheng-Min Yang, Gustavo Pottker
article en
2 citations

Abstract

• First pool boiling evaluation of 2P50 for two-phase immersion cooling • 2P50 shows up to 59% higher heat transfer coefficient (HTC) than HFE-7100 • 2P50’s CHF is comparable but 5.9%–9.9% lower than HFE-7100 under test conditions • Optimized Cooper correlation predicts HTC with 5.3% MAE for 2P50 The growing use of artificial intelligence has led to heavy thermal loads and high heat dissipation rates in data centers. Conventional air-cooled technologies are not able to fulfill these requirements. To overcome these challenges, two-phase immersion cooling (2PIC) has emerged as one of the leading technologies for high power-density chips. 2PIC increases the heat dissipation rate and efficiency of the system while reducing the footprint of the cooling equipment. A fluid with adequate dielectric properties, a suitable normal boiling temperature to maintain chip temperatures, and good material compatibility, is desired for 2PIC system. In this study, the pool boiling heat transfer of a new developmental dielectric fluid, Opteon™ 2P50, was experimentally investigated. The heat transfer coefficients at various heat fluxes (20–150 kW/m 2 ) and the critical heat flux were measured using a smooth aluminum surface. Compared with HFE-7100, Opteon™ 2P50 shows higher heat transfer coefficient (up to 59% higher) and a slightly lower value of critical heat flux (around 5.9% lower). The modified Cooper correlation with the optimized leading constant resulted in reliable prediction accuracy with a 5.3% mean absolute error percentage. Overall, these results indicate that the new dielectric fluid provides similar thermal performance to some legacy fluids.

International Journal of ThermofluidsVol. 29
Oak Ridge National Laboratory (US), DuPont (United States) (US), Chemours (United States)
Affordable and clean energy
Openalex Percentile: Top 18%
Heat Transfer and Boiling Studies
1.43
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Pool boiling heat transfer evaluation of next-generation dielectric fluid: Opteon™ 2P50 — Yifeng Hu, M. Muneeshwaran, et al. · International Journal of Thermofluids (2025) | TGRS Research Map | TGRS