Research on the priority of influencing factors of liquid cooling thermal management in electrochemical energy storage power station

The bottom liquid cooling was studied to analyze the priority order of various factors influencing battery thermal management system (BTMS). A single-factor analysis was conducted to evaluate the impact of individual variables on heat dissipation, including battery layout, spacing and fluid performance parameters. Subsequently, an orthogonal test was used to perform a multi-factor analysis to determine the optimal combination of parameters based on their influence on the BTMS performance. The results of orthogonal test showed that the factors influencing the maximum temperature ( T max ) and temperature difference (△ T ) of the battery module ranked as follow: flow inlet temperature > battery spacing > flow inlet rate. In contrast, the influence on the pressure drop followed the order: flow inlet rate > battery spacing > flow inlet temperature. Based on comprehensive evaluation, the optimal combination of influencing factors was determined to be a battery spacing of 12 mm, a flow inlet rate of 0.012 kg/s, and a flow inlet temperature of 300 K. The research results of this paper provide a valuable reference for the influence factors analysis of liquid cooling thermal management.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2025-08-11
DOI
https://doi.org/10.1016/j.csite.2025.106863
Primary Topic
Advanced Battery Technologies Research
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on the priority of influencing factors of liquid cooling thermal management in electrochemical energy storage power station

Li Jia, Honglei Ren, Zhifeng Chen
Case Studies in Thermal Engineering
Advanced Battery Technologies Research
article

Research on the priority of influencing factors of liquid cooling thermal management in electrochemical energy storage power station

Li Jia, Honglei Ren, Zhifeng Chen
article en

Abstract

The bottom liquid cooling was studied to analyze the priority order of various factors influencing battery thermal management system (BTMS). A single-factor analysis was conducted to evaluate the impact of individual variables on heat dissipation, including battery layout, spacing and fluid performance parameters. Subsequently, an orthogonal test was used to perform a multi-factor analysis to determine the optimal combination of parameters based on their influence on the BTMS performance. The results of orthogonal test showed that the factors influencing the maximum temperature ( T max ) and temperature difference (△ T ) of the battery module ranked as follow: flow inlet temperature > battery spacing > flow inlet rate. In contrast, the influence on the pressure drop followed the order: flow inlet rate > battery spacing > flow inlet temperature. Based on comprehensive evaluation, the optimal combination of influencing factors was determined to be a battery spacing of 12 mm, a flow inlet rate of 0.012 kg/s, and a flow inlet temperature of 300 K. The research results of this paper provide a valuable reference for the influence factors analysis of liquid cooling thermal management.

Case Studies in Thermal EngineeringVol. 74
Beijing Jiaotong University (CN)
National Natural Science Foundation of China
Affordable and clean energy
Openalex Percentile: Top 78%
Advanced Battery Technologies Research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.