A comparative study of cable fire dynamics: bench-scale experiments and numerical simulations with and without fire-retardant coating
Cable fires are one of the primary causes of fire hazards in nuclear power plants (NPPs) and warehouse buildings. This paper presents a study on the experimental and numerical analysis of cable failure with and without fire-resistant coating. The experiments were conducted in two sets under two different average heat fluxes, ranging from 15 (13–15) kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m1"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> to 20 (17–20) kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m2"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> . A total of 10 experiments were analyzed, with five varying fire-resistant coating thicknesses from 0 to 0.8 mm for each heat flux value. For the power cable without coating, under an average heat flux value of 15 kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m3"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> , the failure time was recorded as 1,897 s. Furthermore, the core and outer sheath temperatures at the time of failure, under the same heat flux, were recorded as 282.60°C and 353.90°C, respectively. For the power cable without coating under a heat flux value of 20 kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m4"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> , the failure time was recorded as 991 s; the core and outer sheath temperatures at failure were recorded as 223.16°C and 310.16°C, respectively. Correlations for both heat fluxes were established, showing close agreement with experimental results—within a 2% variation. COMSOL Multiphysics software is used to perform the numerical simulations. The simulation results for the uncoated cable showed that under a heat flux value of 15 kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m5"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> , the failure time, core temperature, and outer sheath temperature were 1898 s, 333.37°C, and 361.83°C, respectively. Under a heat flux value of 20 kW/ <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m6"><mml:mrow><mml:msup><mml:mi>m</mml:mi><mml:mn>2</mml:mn></mml:msup></mml:mrow></mml:math> for a power cable without coating, the simulation results obtained for cable failure time, core temperature, and outer sheath temperature were found to be 990 s, 212.73°C, and 256.45°C, respectively. The absolute mean deviation for the outer sheath in numerical validation was 9.94%, while for the core, it was 14.19%. The simulation results show good agreement with the experimental results. These findings contribute to a better understanding of cable burning characteristics and failure times.
Authors
- Akhil Gupta (ORCID: https://orcid.org/0000-0002-9095-7003)
- Ankit Sharma (ORCID: https://orcid.org/0000-0002-2891-0458)
- Ravi Kumar (ORCID: https://orcid.org/0000-0002-8855-1469)
- Raj Kumar Mishra (ORCID: https://orcid.org/0000-0002-3608-1258)
- Mahesh Kumar Tiwari (ORCID: https://orcid.org/0000-0002-1103-3284)
- Ankit Dasgotra (ORCID: https://orcid.org/0000-0003-2201-4799)
- M. Meena (ORCID: https://orcid.org/0000-0003-4536-3967)
- Pavan K. Sharma (ORCID: https://orcid.org/0009-0007-6777-2856)
Institutions
- Johns Hopkins University (US)
- Indian Institute of Technology Roorkee (IN)
- GD Goenka University (IN)
- Bhabha Atomic Research Center Hospital (IN)
- University of Petroleum and Energy Studies (IN)
Publication Details
- Journal
- Frontiers in Thermal Engineering
- Published
- 2025-08-13
- DOI
- https://doi.org/10.3389/fther.2025.1560746
- Primary Topic
- Fire dynamics and safety research
- Type
- article
- Field-Weighted Citation Impact
- 0.00
Funders
- Indian Institute of Technology Roorkee
- Bhabha Atomic Research Centre